Model IR5500
24
AOd – Analog Output delay
0, 1, 2…10, 15, 20, 25… 60
- Seconds before the F1 fault code becomes
active. Ao1 level changes to bbF, and the Receiver displays fault code F1.
oFd – Output Fault delay
0
to
60
- Minutes before the F3 fault is active. The Ao1 level changes from
bbF to dEt, and the displayed fault code changes from F1 to F3.
ind – IR Input Fault delay
0
to
60
- Minutes before the F12 fault is active. The Ao1 level changes to
inF, and the Receiver displays fault code F12.
diS
– Display options
Pct / AJ
– Display alignment signal strength displayed as percent expected
(Pct) or as a logarithm of signal strength during adjustment (AJ).
Std / FLP
– Display standard or flipped as a mirror image, for reading via
mirror when the display is close to a pipe, tank, wall, or other surface.