Installing Generac PWRcell Battery

Installation Manual for Generac PWRcell Battery

21

Installing Cover

1.

See 

Figure 4-27

Place cover (A) upright in front of 

unit. 

2.

Slide cover straight back until it engages with body
(B).

3.

Verify  all  angled  guides  are  tucked  inside  body. 
The back edges of the cover should be against the 
rubber gasket along their entire length (C). 

NOTE: 

Do not force cover into place.

4.

Lift  straight  up.  Pins  on  cover  will  automatically 
engage and hold the top of the cover in place. 

5.

Gently push in on the bottom of the cover. This will 
lock the bottom of the cover in place.

6.

Peel off the protective plastic sheet from the cover.

7.

Install two M4x16 machine screws (D).

To remove the cover: 

1.

See 

Figure 4-27

Remove M4X16 machine screws 

(D) securing cover (A) to body (B).

1.

Lift cover up.

2.

Pull cover bottom out slightly and lower to the floor.

B

A

C

D

009919

Figure 4-27. Installing Front Cover

Upgrading Generac PWRcell Battery

See 

Figure 4-27

Inside of the Generac PWRcell Battery, 

battery  modules  are  stacked  2-deep  on  three  levels, 
allowing for up to 6 modules to be connected in a series. 
In systems with less than 6 modules, Generac PWRcell 
can be upgraded with additional module up to a total of 6 
modules.
Whenever upgrading Generac PWRcell:

A  Vset  Function  must  be  performed.  See 

Using 

Vset Function

.

A module  spacer  must  be  installed  on  any  single 
module  shelf.  See 

Installing Module Spacer 

(Generac PWRcell 3 and Generac PWRcell 5 
only)

Using Vset Function

NOTE: 

VSet  Function  needs  to  be  performed  before 

installing new battery modles into the Generac PWRcell 
battery. 

To perform Vset Function:

1.

Verify the Generac PWRcell Battery is at 50% state 
of charge or greater.

2.

Perform  Safety  Shutdown  using  inverter  control 
panel.

3.

Measure  new  battery  module  voltages  at  module 
main power terminals using a multimeter set to DC 
volts.

4.

Record the voltage values for each module. If the 
new modules have slightly different readings, aver-
age the values to get a single measurement.

5.

Recover  from  Safety  Shutdown  by  pressing  the 
center button on the inverter control panel.

6.

Change  system  mode  to  Priority  Backup  on  the 
inverter  control  panel  by  choosing  Priority  Back 
and selecting Confirm.

7.

Navigate  to  the  Generac  PWRcell  Battery  device 
page  on  the  inverter  control  panel  using  the  right 
arrow key. 

8.

Select Enable and Confirm to enable the Generac 
PWRcell Battery.

9.

Select Mod Settings on the Generac PWRcell Bat-
tery device page and choose Module Vset. 

10.

Input  the  average  voltage  value  from  step  4  then
scroll  to  the  bottom  of  the  menu  to  commit  the 
change.

11.

Use  the  arrow  keys  to  navigate  to  the  Generac 
PWRcell  Inverter  device  page  and  select  Enable 
and Confirm.

12.

Use the arrow keys to return to the Generac PWR-
cell Battery device page and press the center but-
ton.

Содержание PWRcell 3

Страница 1: ...Loss of life This product is not intended to be used in a critical life support application Failure to adhere to this warning could result in death or serious injury Register your Generac product at...

Страница 2: ...ation is performed promptly and to have the equipment checked periodically by an ASD Normal maintenance service and replacement of parts are the responsibility of the owner operator and as such are no...

Страница 3: ...ing Feet 15 Installing REbus wiring 15 Connecting Blackstart Battery 16 Installing Battery Modules 16 Installing Rear Modules 17 Installing Grounding Tabs 17 Installing Front Modules 17 Installing Mod...

Страница 4: ...iv Installation Manual for Generac PWRcell Battery This page intentionally left blank...

Страница 5: ...ng placement operation and maintenance of the unit and its components Always supply this manual to any individual that will use this unit and instruct them on how to correctly start operate and stop t...

Страница 6: ...to be used in a critical life support application Failure to adhere to this warning could result in death or serious injury 000598 WARNING Equipment damage Connect only to REbus compatible devices Nev...

Страница 7: ...al help Failure to do so will result in death or serious injury 000599 DANGER Electrocution Turn battery disconnect OFF and de energize REbus before touching terminals Failure to do so will result in...

Страница 8: ...000147 WARNING Risk of Fire Unit must be positioned in a manner that prevents combustible material accumulation underneath Failure to do so could result in death or serious injury Safety Shutdown 0006...

Страница 9: ...ic codes This unit must be installed in accordance with current NFPA and ICC standards and any other federal state and local codes for minimum distances from other structures Standards Index 000209b W...

Страница 10: ...Safety Rules General Information 6 Installation Manual for Generac PWRcell Battery This page intentionally left blank...

Страница 11: ...REbus Communication Protocol REbus DC Nanogrid Voltage Input Output VDC 360 420 Round Trip Efficiency DC to DC 96 5 Temperature Operating Temperature Limits F C 41 113 5 45 Recommended Temperature Ra...

Страница 12: ...d nameplate Record the information from these tags so it is available if the tags are lost or damaged When ordering parts or requesting assistance you may be asked to provide this information A 000989...

Страница 13: ...Generac PWRcell products use the REbus 380VDC nanogrid to connect energy sources storage and loads The REbus nanogrid automates the flow of power to enable plug and play setup and operation of Genera...

Страница 14: ...om the battery monitoring system BMS electronics NOTE Battery Disconnect can be locked in the OFF position if required NOTE Turn Battery Disconnect OFF whenever system will be powered down and left in...

Страница 15: ...ith local building code Do not expose the Generac PWRcell Battery to extreme temperatures See Specifications for rec ommended and acceptable operating tempera tures Operating the Generac PWRcell Batte...

Страница 16: ...for correct DC wiring coloring NEC 210 5 C 2 for identification of DC conduc tors carrying more than 50V Always adhere to applicable codes when marking and installing DC conductors See Table 3 2 For...

Страница 17: ...To remove slide cover toward the top of the unit swing the bottom out and pull cover down 8 Set cover aside in a safe place NOTE Do not adjust the feet at this time The feet are shipped pre positioned...

Страница 18: ...rac PWRcell Battery 14 Installation Manual for Generac PWRcell Battery Figure 4 2 Generac PWRcell Battery Rear View 009925 67 7 in 1 7 m 22 2 in 563 1 mm Figure 4 3 Generac PWRcell Battery Front View...

Страница 19: ...Safety Shutdown before installing wiring If there are any other batteries connected to REbus toggle their front Battery Disconnect switches to OFF Failure to do so will result in death or serious inj...

Страница 20: ...Figure 4 8 Connect blackstart battery lead to battery terminal E NOTE One lead is already connected to terminal F 2 Record model serial number and date of pur chase on front cover of this manual F 009...

Страница 21: ...nto the battery module case to provide an equipment grounding connection G H K J I 009929 Figure 4 11 Installing Rear Battery Modules Installing Grounding Tabs 1 See Figure 4 12 Install two L shaped g...

Страница 22: ...le 5 Module Spacer Kit for part number Table 5 Module Spacer Kit Module Spacer Kit Part Number Generac PWRcell Spacer Kit HMSK101 To install module spacer 1 See Figure 4 16 Angle top of spacer P under...

Страница 23: ...e 4 21 Retention Clips 3 of 3 2 Apply gentle pressure to ensure all grounding tabs and clips make firm contact with case 3 Secure retention clip to bracket with M4X8 screw Connecting COM Cables 1 See...

Страница 24: ...CAT5 K Orange CAT5 L Black CAT5 Jumpers Connecting Battery Power Cable 000639 DANGER Electrocution Never reach into port or touch battery terminals with hands or tools Doing so will result in death se...

Страница 25: ...Using Vset Function A module spacer must be installed on any single module shelf See Installing Module Spacer Generac PWRcell 3 and Generac PWRcell 5 only Using Vset Function NOTE VSet Function needs...

Страница 26: ...switch on the front of the Generac PWRcell Bat tery 17 Add the new modules into the string by connecting power and communications cables in the appropri ate sequence See Installing Battery Modules 18...

Страница 27: ...Select desired operational mode using the Gen erac PWRcell Inverter control panel 4 Enable the Generac PWRcell Inverter to energize the REbus nanogrid Configure Generac PWRcell 1 Select Mod Settings...

Страница 28: ...ice Dealer shall prepare a written decommissioning plan that provides the overview of the decommissioning process developed specifically for the Generac PWRCell Battery system that is to be decommissi...

Страница 29: ...horized Service Dealer IASD or Generac Customer Service at 1 888 436 3722 1 888 GENERAC Table 6 1 General Troubleshooting Guide Problem Possible Cause Solution Battery remains in Waiting state Battery...

Страница 30: ...Troubleshooting 26 Installation Manual for Generac PWRcell Battery This page intentionally left blank...

Страница 31: ...n 7 Wiring Diagrams Generac PWRcell 3 009945 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC BLACK RED Module CAT5 COMs Cable Module Jumper...

Страница 32: ...PWRcell Battery Generac PWRcell 4 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC BLACK RED Module CAT5 COMs Cable Module Jumpers Top Back...

Страница 33: ...ry 29 Generac PWRcell 5 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC Top Back Front BLACK RED Module CAT5 COMs Cable Module 5 Module 4 M...

Страница 34: ...PWRcell Battery Generac PWRcell 6 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC Top Back Front BLACK RED Module CAT5 COMs Cable Module 6...

Страница 35: ......

Страница 36: ...ghts reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: