Installing Generac PWRcell Battery
16
Installation Manual for Generac PWRcell Battery
To install REbus wiring:
1.
See
. Install REbus conductors to their
terminal blocks: RE+ to red (A), RE- to blue (B).
2.
Install equipment grounding conductor to green ter-
minal block (C).
3.
If required, route field wiring conductors through
the grommet wiring chase baffle (D).
NOTE:
Do not route wires around the baffle.
4.
At the Generac PWRcell Inverter, install RE+ and
RE- conductors to any unused 30A REbus breaker.
5.
Secure equipment grounding conductor to the
Generac PWRcell Inverter ground bar.
A
C
B
D
009928
Figure 4-7. REbus Wiring
Connecting Blackstart Battery
1.
See
. Connect blackstart battery lead to
battery terminal (E).
NOTE:
One lead is already connected to terminal (F).
2.
Record model, serial number, and date of pur-
chase on front cover of this manual.
F
009928
E
Figure 4-8. Blackstart Battery Connections
Installing Battery Modules
NOTE:
Record battery module serial numbers prior to
installation.
See
. When installing battery modules, install
top, rear module (A) first, regardless of configuration.
A
009900
Figure 4-9. Installing Battery Modules
See
for the order of battery module and
spacer installation for Generac PWRcell 3 (B), Generac
PWRcell 4 (C), Generac PWRcell 5 (D), and Generac
PWRcell 6 (E).
NOTE:
Module spacers (F) are required on Generac
PWRcell 3 (B) and 5 (D) configurations.
1
2
3
4
1
2
3
4
1
2
3
4
5
6
1
2
3
4
5
6
009899
E
D
C
B
F
F
Figure 4-10. Battery Module/Spacer Order of Installation