Generac Power Systems PWRcell 3 Скачать руководство пользователя страница 15

Location and Compliance

Installation Manual for Generac PWRcell Battery 

11

Section 3: Location and Compliance

Location and Clearances

Install the Generac PWRcell Battery in dwelling units in 
the following permitted locations only:

Attached  garages  separated  from  dwelling  unit 
habitable spaces in accordance with local building 
code.

Detached garages and accessory structures.

Enclosed  utility  closets  and  storage  or  utility 
spaces.

Basements.

NOTE: 

Refer  to  the  local  Building  Code  for  permitted 

locations for commercial installations.

When selecting a location, consider the following:

Install in protected indoor locations only. If the room 
or space where the Generac PWRcell Battery is to 
be installed is not finished, the wall and ceilings of 
the room or space shall be protected with not less 
than 5/8 in (15.875 mm) Type X gypsum board.

Do not install in any habitable room within a dwell-
ing unit.

Install only in a clean, dry, well ventilated location.

Do  not  allow  bottom  or  front  vents  to  become 
blocked.

The Generac PWRcell Battery installation location 
must meet the working space requirements in NEC 
Article 110.26.

If installed in a garage or other location where the 
Generac PWRcell Battery could be damaged by a 
vehicle, the Generac PWRcell Battery must be pro-
tected  by  approved  barriers  that  are  installed  in 
accordance  with  local  building  code.  Consult  with 
your local AHJ to verify if barriers are required.

Interconnected  smoke  alarms  must  be  installed 
throughout  the  dwelling  unit,  including  rooms, 
attached garages, and areas in which the Generac 
PWRcell  Battery  is  installed  in  accordance  with 
local building codes. If the Generac PWRcell Bat-
tery  is  installed  in  an  attached  garage  or  area 
where smoke alarms cannot be installed in accor-
dance  with  their  listing,  an  interconnected  listed 
heat alarm must be installed and connected to the 
smoke  alarm  system  in  accordance  with  local 
building code.

Do  not  expose  the  Generac  PWRcell  Battery  to 
extreme temperatures. 

See 

Specifications 

for rec-

ommended  and  acceptable  operating  tempera-
tures.  Operating  the  Generac  PWRcell  Battery 
outside  of  the  recommended  range  may  degrade 
performance. 

NOTE: 

Consider  year-round  temperature  extremes 

when  choosing  a  location.  In  extreme  climates,  always 
install Generac PWRcell in a conditioned space. Generac 
recommends  installing  Generac  PWRcell  in  a  condi-
tioned space regardless of climate.

See 

Table

 

3-1

.  E

nsure  minimum  clearances  are 

met. 

Table 3-1. Minimum Airspace Clearances

Sides

2”

Recommend at least 2” on each side 
to operate cover.

Top

3”

Recommend at least 3” on top so 
installer can lift body onto mounting 
bracket.

Front

36”

Recommend at least 36” in front for 
maintenance/service.

Compliance

(000190)

DANGER

Loss of life. Property damage. Installation must always 
comply with applicable codes, standards, laws and  
regulations. Failure to do so will result in death  
or serious injury.  

WARNING

(000257)

Electrocution. Refer to local codes and standards 
for safety equipment required when working with a 
live electrical system. Failure to use required safety 
equipment could result in death or serious injury.

(000182a)

WARNING

Equipment damage. Only qualified service personnel may 
install, operate, and maintain this equipment. Failure to 
follow proper installation requirements could result in death, 
serious injury, and equipment or property damage.

Follow  all  instructions  included  in  this  manual  and  use 
appropriate  practices  for  all  product  wiring  and  installa-
tion.

NOTE: 

It  is  the  responsibility  of  the  installer  to  ensure 

conformance  with  NFPA70E, Article  120,  lockout/tagout 
procedures. If the Generac PWRcell Inverter is installed 
out of sight of the AC distribution panel, a correctly rated 
disconnect  switch  must  be  installed  within  sight  of  the 
PWRcel  Inverter.  In  the  situation  where  the  Generac 
PWRcell Inverter is installed out of sight of the Generac 
PWRcell Battery product, a correctly rated DC disconnect 
switch  must  be  installed  within  sight  of  the  Generac 
PWRcell Battery.

Содержание PWRcell 3

Страница 1: ...Loss of life This product is not intended to be used in a critical life support application Failure to adhere to this warning could result in death or serious injury Register your Generac product at...

Страница 2: ...ation is performed promptly and to have the equipment checked periodically by an ASD Normal maintenance service and replacement of parts are the responsibility of the owner operator and as such are no...

Страница 3: ...ing Feet 15 Installing REbus wiring 15 Connecting Blackstart Battery 16 Installing Battery Modules 16 Installing Rear Modules 17 Installing Grounding Tabs 17 Installing Front Modules 17 Installing Mod...

Страница 4: ...iv Installation Manual for Generac PWRcell Battery This page intentionally left blank...

Страница 5: ...ng placement operation and maintenance of the unit and its components Always supply this manual to any individual that will use this unit and instruct them on how to correctly start operate and stop t...

Страница 6: ...to be used in a critical life support application Failure to adhere to this warning could result in death or serious injury 000598 WARNING Equipment damage Connect only to REbus compatible devices Nev...

Страница 7: ...al help Failure to do so will result in death or serious injury 000599 DANGER Electrocution Turn battery disconnect OFF and de energize REbus before touching terminals Failure to do so will result in...

Страница 8: ...000147 WARNING Risk of Fire Unit must be positioned in a manner that prevents combustible material accumulation underneath Failure to do so could result in death or serious injury Safety Shutdown 0006...

Страница 9: ...ic codes This unit must be installed in accordance with current NFPA and ICC standards and any other federal state and local codes for minimum distances from other structures Standards Index 000209b W...

Страница 10: ...Safety Rules General Information 6 Installation Manual for Generac PWRcell Battery This page intentionally left blank...

Страница 11: ...REbus Communication Protocol REbus DC Nanogrid Voltage Input Output VDC 360 420 Round Trip Efficiency DC to DC 96 5 Temperature Operating Temperature Limits F C 41 113 5 45 Recommended Temperature Ra...

Страница 12: ...d nameplate Record the information from these tags so it is available if the tags are lost or damaged When ordering parts or requesting assistance you may be asked to provide this information A 000989...

Страница 13: ...Generac PWRcell products use the REbus 380VDC nanogrid to connect energy sources storage and loads The REbus nanogrid automates the flow of power to enable plug and play setup and operation of Genera...

Страница 14: ...om the battery monitoring system BMS electronics NOTE Battery Disconnect can be locked in the OFF position if required NOTE Turn Battery Disconnect OFF whenever system will be powered down and left in...

Страница 15: ...ith local building code Do not expose the Generac PWRcell Battery to extreme temperatures See Specifications for rec ommended and acceptable operating tempera tures Operating the Generac PWRcell Batte...

Страница 16: ...for correct DC wiring coloring NEC 210 5 C 2 for identification of DC conduc tors carrying more than 50V Always adhere to applicable codes when marking and installing DC conductors See Table 3 2 For...

Страница 17: ...To remove slide cover toward the top of the unit swing the bottom out and pull cover down 8 Set cover aside in a safe place NOTE Do not adjust the feet at this time The feet are shipped pre positioned...

Страница 18: ...rac PWRcell Battery 14 Installation Manual for Generac PWRcell Battery Figure 4 2 Generac PWRcell Battery Rear View 009925 67 7 in 1 7 m 22 2 in 563 1 mm Figure 4 3 Generac PWRcell Battery Front View...

Страница 19: ...Safety Shutdown before installing wiring If there are any other batteries connected to REbus toggle their front Battery Disconnect switches to OFF Failure to do so will result in death or serious inj...

Страница 20: ...Figure 4 8 Connect blackstart battery lead to battery terminal E NOTE One lead is already connected to terminal F 2 Record model serial number and date of pur chase on front cover of this manual F 009...

Страница 21: ...nto the battery module case to provide an equipment grounding connection G H K J I 009929 Figure 4 11 Installing Rear Battery Modules Installing Grounding Tabs 1 See Figure 4 12 Install two L shaped g...

Страница 22: ...le 5 Module Spacer Kit for part number Table 5 Module Spacer Kit Module Spacer Kit Part Number Generac PWRcell Spacer Kit HMSK101 To install module spacer 1 See Figure 4 16 Angle top of spacer P under...

Страница 23: ...e 4 21 Retention Clips 3 of 3 2 Apply gentle pressure to ensure all grounding tabs and clips make firm contact with case 3 Secure retention clip to bracket with M4X8 screw Connecting COM Cables 1 See...

Страница 24: ...CAT5 K Orange CAT5 L Black CAT5 Jumpers Connecting Battery Power Cable 000639 DANGER Electrocution Never reach into port or touch battery terminals with hands or tools Doing so will result in death se...

Страница 25: ...Using Vset Function A module spacer must be installed on any single module shelf See Installing Module Spacer Generac PWRcell 3 and Generac PWRcell 5 only Using Vset Function NOTE VSet Function needs...

Страница 26: ...switch on the front of the Generac PWRcell Bat tery 17 Add the new modules into the string by connecting power and communications cables in the appropri ate sequence See Installing Battery Modules 18...

Страница 27: ...Select desired operational mode using the Gen erac PWRcell Inverter control panel 4 Enable the Generac PWRcell Inverter to energize the REbus nanogrid Configure Generac PWRcell 1 Select Mod Settings...

Страница 28: ...ice Dealer shall prepare a written decommissioning plan that provides the overview of the decommissioning process developed specifically for the Generac PWRCell Battery system that is to be decommissi...

Страница 29: ...horized Service Dealer IASD or Generac Customer Service at 1 888 436 3722 1 888 GENERAC Table 6 1 General Troubleshooting Guide Problem Possible Cause Solution Battery remains in Waiting state Battery...

Страница 30: ...Troubleshooting 26 Installation Manual for Generac PWRcell Battery This page intentionally left blank...

Страница 31: ...n 7 Wiring Diagrams Generac PWRcell 3 009945 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC BLACK RED Module CAT5 COMs Cable Module Jumper...

Страница 32: ...PWRcell Battery Generac PWRcell 4 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC BLACK RED Module CAT5 COMs Cable Module Jumpers Top Back...

Страница 33: ...ry 29 Generac PWRcell 5 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC Top Back Front BLACK RED Module CAT5 COMs Cable Module 5 Module 4 M...

Страница 34: ...PWRcell Battery Generac PWRcell 6 Contactors REbus 380v DC REbus cable entrance G R B I O Switch Black start battery Snubber Battery String DC Top Back Front BLACK RED Module CAT5 COMs Cable Module 6...

Страница 35: ......

Страница 36: ...ghts reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Отзывы: