ENGLISH
55
5.8 “VOLT” working mode
The voltage supplied to the pump (through the input signal) determines the proportional dosing according
to the two minimum and maximum values of strokes per minute set during programming.
When to use this mode?
This mode is useful when an external signal in voltage is available and it is necessary to properly dose a
product in the set quantities.
Which parameters must be set?
HIV (high voltage)
LOV (low voltage)
SPM (strokes per minute)
To work in this mode it is necessary to set the values of “HIV” (high
operating voltage), “LOV” (low operating voltage) and “SPM” (strokes
per minute) that pump will produce when getting close to the set
values.
To set these values enter “VOLT” setup mode. The cursor will start
blinking on the first digit near “HIV” field. Enter the high voltage value
that will be supplied to the pump (“UP” key). To move to next digit
(unit) press “
RIGHT
” key.
Then the cursor will blink on the first digit of the “SPM” field. Enter the
strokes that pump will produce near “HIV” value (“
UP
” key) previously
set. To move to next digit press “
RIGHT
” key again.
Press “
P
” key to move to “LOV”. The cursor will start blinking on first
digit near to “LOV” field. Enter the low operating voltage value that will
be supplied to the pump (“
UP
” key).
To move on next digit (unit) press “RIGHT” key.
Then the cursor will blink on the first unit of the “SPM” field. Enter the
strokes that pump will produce near “LOV” value (“
UP
” key). To move
to next digit press “
RIGHT
” key.
Press “
P
” key to save the entered data and “
ESC
” to exit to main
menu or only press “
ESC
” to exit without saving.
Attention
: if a wrong value is set (for instance, the same value for HIV and LOV has been set), an error
message (
WRONG ENTRY
) will appear. Set correct parameters.
mode ( 08 )
volt
hiv 10.0
spm: 100
lov 00.0
spm: 000
Tasto
Tasto
Tasto
Key
Key
Key