Geist Watchdog Wi Instruction Manual
68
© 2017
GM1212 Geist Watchdog Wi Instruction Manual
Once you apply the global settings, that value will be present on each sensor’s individual
configuration page. The global settings will not be recorded on this page - when you click
to go to another page of the user interface and then return to this global settings page, all
the values in the alarm fields will have reverted back to zeros.
Figure 4-36 Alarms Page
Alarms Configuration Options
Option Description
Clear All Alarms
Click this button to clear all active alarms on this Watchdog Wi. The
Watchdog Wi will re-send an alarm after a point has been in alarm for
a certain number of hours.
Select a re-alarm time from 1-24 hours. Set the re-alarm time to 0 to
disable the feature. Default: 0 (disabled)
Global Alarm Settings - There is a checkbox next to each individual alarm setting. Check
this box to apply that particular setting to each sensor in the system. If you do not check
the check-box next to the alarm parameter, that value will not be applied to the sensors in
your system.
Temp. Over
Enter a high temperature alarm threshold - if the temperature rises
above this value, a high temperature alarm is generated. Check the
box to activate the option, and enter a temperature value.
Temp. Under
Enter a low temperature alarm threshold - if the temperature drops
below this value, a low temperature alarm is generated. Check the
box to activate the option, and enter a temperature value.
Humidity Over
Enter a high humidity alarm threshold - if the humidity rises above
this value, a high humidity alarm is generated. Check the box to
activate the option, and enter a humidity value.