AFE200 • Instruction Manual
99
Example of calculation of scale factor
Analog out x scale
:
To display the drive speed, use an analog instrument with field of measurement from
0...2V. This means that, to display the speed of the drive, a voltage of 2V on the ana-
log output of the drive must correspond to the maximum speed. With a scale factor of
1 this would be 10V (Scale factor = 2V / 10 V = 0.200).
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
10.5
1816 Analog out 1 mon
cnt
INT16
0
0
0
ER
The value of the actual voltage present on analog output 1 is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
10.6
1818 Analog out 2 mon
cnt
INT16
0
0
0
ER
The value of the actual voltage or current present on analog output 2 is displayed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
10.7
1824 An out 1 sign src
LINK
16
6000
0
16384 ERW
10.8
1826 An out 2 sign src
LINK
16
6000
0
16384 ERW
L�DIGSEL2
Selection of the origin (source) for the signal that determines the sign of the relative
analog output. The terminal to be associated with this function can be selected from
the “L_DIGSEL2” selection list.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
10.9
1832 Analog out 1 min
cnt
INT16
-16384
-32768
+32767 ERW
10.10
1834 Analog out 1 max
cnt
INT16
16384
-32768
+32767 ERW
Setting of the minimum and maximum values for the analog output for the voltage
present on analog output 1.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
10.11
1840 Analog out 2 min
cnt
INT16
-16384
-32768
+32767 ERW
10.12
1842 Analog out 2 max
cnt
INT16
16384
-32768
+32767 ERW
Setting of the minimum and maximum values for the analog output for the voltage
present on analog output 2.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
10.13
1848 Analog out 2 type
ENUM
-10V..+10V
0
2
ERW
Selection of the type of output (in voltage or current). Depending on the output signal,
move the switch on the regulation card. The standard output is coded for the signal in
voltage.
0
0..20mA
1
4..20mA
2
-10V..+10V
Select option
0
in order to apply a maximum voltage of ±12.5V (typically ±10V/5mA) to
analog output 2.