6 - COMMANDS
It is possible to work in
Local
or
Remote
mode.
When switching between
Remote
and
Local
modes the origin of the
Enable
and
Start
commands is
switched.
In
Remote
mode the “
Commands remote sel
” parameter is used to configure the source of the
Enable
and
Start
commands which can be
Terminal
(standard digital input, expansion digital input) or
Digital
(Modbus, Fieldbus).
In
Local
mode the PAR1002 “
Commands local sel
” parameter is used to configure the source of the
Enable
and
Start
commands, which can be
Terminal
(standard digital input, expansion digital input)
or
Keypad
(Start key, Stop key).
In
Remote
->
Digital
mode the
PAR 1018 Digital Enable src
must be used to configure the source.
Normally the sources are the
Pad
parameters. Modbus or Fieldbus must therefore write the desired
value on the
Pad
parameters. Alternatively, the value of 6000 can be written directly on the
Digital
Enable src
parameter for a source of
Null
(0) or the value of 6002 for a source of
One
(1).
Another alternative is to configure the
Digital Enable src
source on the
PAR 4454 ... 4484 BitX de-
comp mon
parameters, so that the Modbus or Fieldbus can then write the desired value on the
PAR
4450 Dig word decomp
parameter.
Local
< >
Remote
switching is performed with the variable value configured as
Loc/Remote src
, i.e.
it can be a standard digital input, expansion digital input, Modbus, Fieldbus, Dig Local/Remote.
In the default condition, the associated variable is
Dig Local/Remote
, which is written by the
LOC
key
from the keypad: switching is thus performed by pressing the
LOC
key.
For safety reasons,
Local
< >
Remote
switching is only performed with Terminal Enable = 0.
Example 1
With the machine in automatic operating mode, the drive works in Remote -> Digital -> Fieldbus mode.
With the machine in manual operating mode, the drive works in Local -> Terminal -> Standard digital
input mode.
If switching from automatic to manual machine operation, the drive must switch between Remote and
Local mode. The switch command must be sent via standard digital input or fieldbus.