AFE200 • Instruction Manual
v
outm
= 400v
ca
ηm
= 0,96
I
m
= 43a
Application: continuous load, Pcont= 80%
Requested overload = 150%
> Total electrical power absorbed:
P
tot
=
(P
outm
* P
cont
)
η
m
P
tot
=
(18.5 * 0.85)
+
(18.5 * 0.9)
+
(22 * 0.8)
= 52.4 kW
0.95
0.95
0.96
> Total power requested by the DC-link side:
P
tot
=
P
tot
+
52.4
= 52.4 kW
ηd
0.97
400 Vac mains, corresponding DC-link value = 650Vcc
P
tot
=
P
dc
* 1000
+
54000
= 52.4 kW
Vdc-link
650
The AFE200 must be capable of delivering a current of ≥ 83A.
Choose the size with the appropriate characteristics from the section 10.6:
AFE200 - 4450.
> Choosing the drive:
Since the motors are used at below the rated power, the following inverters are
suitable:
Motor 1 :
I
m
1
= 37A * 85% = 31.4A
Choose the size with the rated current required by the motor (≥ 31.4A) from the
catalogue ADV & AFE (section ADV200-DC “2.7 Output Data” on page 37).
With a 650 Vdc drive:
ADV-3185-...-DC (In = 34.2A, OK).
Motor 2 :
I
m
2
= 37A * 90% = 33.3A
Choose the size with the rated current required by the motor (≥ 33.3A) from the
catalogue ADV & AFE (section ADV200-DC “2.7 Output Data” on page 37).
With a 650 Vdc drive:
ADV-3185-...-DC (In = 34.2A, OK).