AFE200 • Instruction Manual
115
10
Par 32
If set to
0
the channel is not assigned.
If set to
1
the datum is assigned a 16-bit count.
If set to
2
the datum is assigned a 32-bit count.
If set to
3
16 bits on the channel are reserved for the datum, not used.
If set to
4
32 bits on the channel are reserved for the datum, not used.
If set to
5
the datum is assigned a 16-bit count used by MDPLC.
If set to
6
the datum is assigned a 32-bit count used by MDPLC.
If set to
7
the datum is assigned engineering units on a 16-bit integer.
If set to
8
the datum is assigned engineering units on a 32-bit integer.
If set to
9
, the datum is assigned a 16-bit integer engineering unit format not in real
time (5-10ms)
If set to
10
the datum is assigned a 32-bit integer engineering unit format or float for-
mat if the associated parameter is a float-type parameter not in real time (5-10ms)
Note!
If the
sys
parameter is not assigned, none of the subsequent fieldbus channels are read, even if
programmed.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
14.3.3
4024 Fieldbus M->S1 mon
INT32
32
0
0
0
ER
14.3.7
4034 Fieldbus M->S2 mon
INT32
32
0
0
0
ER
14.3.11 4044 Fieldbus M->S3 mon
INT32
32
0
0
0
ER
14.3.15 4054 Fieldbus M->S4 mon
INT32
32
0
0
0
ER
14.3.19 4064 Fieldbus M->S5 mon
INT32
32
0
0
0
ER
14.3.23 4074 Fieldbus M->S6 mon
INT32
32
0
0
0
ER
14.3.27 4084 Fieldbus M->S7 mon
INT32
32
0
0
0
ER
14.3.31 4094 Fieldbus M->S8 mon
INT32
32
0
0
0
ER
14.3.35 4104 Fieldbus M->S9 mon
INT32
32
0
0
0
ER
14.3.39 4114 Fieldbus M->S10 mon
INT32
32
0
0
0
ER
14.3.43 4124 Fieldbus M->S11 mon
INT32
32
0
0
0
ER
14.3.47 4134 Fieldbus M->S12 mon
INT32
32
0
0
0
ER
14.3.51 4144 Fieldbus M->S13 mon
INT32
32
0
0
0
ER
14.3.55 4154 Fieldbus M->S14 mon
INT32
32
0
0
0
ER
14.3.59 4164 Fieldbus M->S15 mon
INT32
32
0
0
0
ER
14.3.63 4174 Fieldbus M->S16 mon
INT32
32
0
0
0
ER
The value received from the bus is displayed. This parameter must be associated with
the src parameter to enable the
M->S
channel.
The user may modify the
M->S
and by
S->M sys
parameters. The consistency of the
sys with the parameter assigned to the channel is checked.
Check for channels M->S:
Sys parameter
FB type
result
Count 32
32 bit
Receives 32 bits from FB and copies to 32 bits of monitor. OK
32_H
Receives 32 bits from FB and copies to 32 bits of monitor. OK
32_L
Receives 32 bits from FB and copies to 32 bits of monitor. OK
Count 16
16 bit
Receives 16 bits from FB and doesn’t know whether to copy to 16H or 16L of
monitor. Error