128
AFE200 • Instruction Manual
20
External fault
21
Emg stop alarm
22
Power down
23
Prc fbk loss
24
Not Used1
25
Not Used2
26
Not Used3
27
Not Used4
28
Not Used5
29
Not Used6
30
Not Used7
31
Not Used8
3
2 Not Used9
3
3 Plc1 fault
3
4 Plc2 fault
3
5 Plc3 fault
3
6 Plc4 fault
3
7 Plc5 fault
3
8 Plc6 fault
3
9 Plc7 fault
4
0 Plc8 fault
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.37
4720 Alm autoreset time
s
FLOAT
0.0
0.0
60.0
ERW
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the AFE product is set to restart.
If some alarms are still enabled the AFE product is set to execute a new attempt at
automatic reset.
At each attempted reset a counter increases. If the limit set in the
PAR 4722 Alm
autoreset number
parameter is reached the AFE product is set to make no more at-
tempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no
alarms are enabled.
If the parameter is 0 the function is disabled.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.38
4722 Alm autoreset number
UINT16
20
0
100
ERW
Setting of the maximum number of attempted automatic resets.