AFE200 • Instruction Manual
139
9 - Troubleshooting
9.1 Alarms
Note !
To reset alarms, see Quick start guide,
paragraph 6.6.1
.
In the following table, the Code is visible only from serial line.
Code
Error message shown
on the display
Sub-code
Description
0
No alarm
Condition: No alarm present
1
Overvoltage
Condition: DC link overvoltage alarm due to energy recovered from the motor. The voltage
supplied to the drive power section is too high with respect to the maximum limit.
Solution:
- Increase the bandwidth of the voltage regulator (if the problem occurs under dynamic condi-
tions)
- Use a larger drive.
2
Undervoltage
Condition: DC link undervoltage alarm.
The voltage arriving at the drive power section is too low compared to the minimum threshold
relating to the 560
Mains voltage
parameter setting due to:.
- the mains voltage being too low or overextended voltage drops.
- poor cable connections (e.g. loose contactor terminals, inductance, filter, etc. ).
Solution: Check the connections and measure the mains voltage.
3
Ground fault
Condition: Ground short circuit alarm
Solution:
- Check the drive and pre-load circuit wiring.
4
Overcurrent
Condition: Instantaneous overcurrent protection intervention alarm.
This may be due to the incorrect setting of current regulator parameters or a short circuit betwe-
en phases or ground fault on the drive output.
Solution:
- Check the current regulator parameters
- Check the wiring to the mains and make sure the mains phases match those of the synchro-
nisation card.
5
Desaturation
Condition: Instantaneous overcurrent in the IGBT bridge alarm.
Solution:
Switch the drive off and then switch it on again.
If the alarm persists, contact the technical service centre.
6
MultiUndervolt
Condition:
The number of attempted automatic restarts after the
Undervoltage
alarm has exce-
eded the set
PAR 4650 Underv res attempt
value in the
PAR 4652 Underv res delay time
.
Solution:
Too many
Undervoltage
alarms.
Adopt the proposed solutions for the
Undervoltage
alarm.
7
MultiOvercurr
Condition:
2 attempted automatic restarts after the
Overcurrent
alarm within 30 seconds. If
more than 30 seconds pass after the
Overcurrent
alarm was generated, the attempt counter is
reset.
Solution:
Too many
Overcurrent
alarms. Adopt the proposed solutions for the
Overcurrent
alarm
8
MultiDesat
Condition:
2 attempted at automatic restarts after the
Desaturation
alarm within 30 seconds.
If more than 30 seconds pass after the
Desaturation
alarm was generated, the attempt counter
is reset.
Solution:
Too many
Desaturation
alarms.
Adopt the proposed solutions for the
Desaturation
alarm.
9
Undervolt AC
Condition: The measured mains voltage is too low