IST-1408.PA01.02 - Dis.0534045
CE408P / User Manual
Pag. 6/41
GECA S.r.l. - Via E. Fermi, 98 25064 GUSSAGO (BS) - Tel. 030 3730218 - Fax 030 3730228
THE FOLLOWING INSTRUCTIONS DESCRIBES ALL THE CENTRAL SYSTEM
SETUP PROCEDURES AS WELL AS THE INSTALLATION PROCEDURES TO
BE EXECUTED ONLY BY AUTHORISED AND EXPERIENCED PERSONNEL.
CE408P INSTALLATION
The
CE408P
should be mounted on the wall using 3 screws and wall plugs (Ø 6 mm) or 3 M4 screws
and nuts, if the wall is not in masonry. The housing's base must be fixed through the 3 holes, one in
the center and the other in the bottom corners
(
Fig.2
). The electrical connections should be executed
all on the housing base.
Inside the housing, it can also accommodate
two 12V/1.3Ah Lead batteries
connected in series
(
Fig.3
) to
assure the system powering in case of mains blackout. The battery life is about 30 minutes with 8
sensors. (The
batteries are not included in the delivery, but are available on request
).
If required, to increase the autonomy (1 hour), it can be used two 7Ah batteries connected in
series, but causes the greatest dimension, shall be installed in a case outside the CE408P.
ELECTRICAL CONNECTIONS
The electrical connections should be executed all on the housing base.
To simplify installation, the housing cover may be detached from the base, by disconnecting the flat
cable, press on the two tabs on each side as shown in
Fig. 3
. To reconnect, simply push the flat cable
into the connector respecting the polarization, the two locking levers will close automatically.
The details of the connections to the mains, the two batteries, the AUX input and relay output
R9 are illustrated
in Figure 3
.
While the details of the connections to the sensors and the other
outputs are illustrated
in Figure 4
.
The terminals are of "polarized inlet" type (1). We suggest to use lugs adequate to the
conductors (2) and to fix the wires to the box structure to avoid excessive stress to the circuits
and to the terminals. Use a screwdriver (3) of the right dimensions.
93mm
Fig 2 – CE408P Dimensions and Template for wall mounting
The cover opens by unscrewing the 4 Allen screws
229 mm
n.3 holes Ø 5mm
2.5