This procedure must be performed with extreme caution, by authorized and 
trained personnel, as they are activated, the relay outputs, which activate the 
devices connected to both the internal functions of the central.

 

SERVICE 

In this submenu you can manage the maintenance of the unit. ------------

 

 
 
 
 

ELECTRIC  TEST  (Level  2)

:  Pressing 

 

ENTER

 

  on  the  relevant  item, 

submenu will appear where you can choose which tests to perform.-----

 

To start a test, press 

 

ENTER

 

 on its item: 

 

DISPLAY:

  Check  the  display  operation,  all  the  pixels  are  lit  in 

sequence. After 3 seconds, return to the previous screen. 

 

KEYBOARD:

 Check the key operation. Will appear the screen with 

the name of the keys, such as places in the keyboard. When a key 
is pressed, the display is shown the corresponding name. 

To return to the previous screen press 

 

ESC

 

  twice. 

 

LED/BUZZER: 

Check  the  operation  of  the  LEDs  and  buzzer.  First,  the  LEDs  switches  off,  and 

then  turn  them  on in  sequence,  Yellow,  Green  and  Red,  then for  1  second  activate  the  buzzer. 
Then automatically returns to the previous screen. 

 

OUTPUTS:

 Check the operation of the relay outputs. Are displayed, the numbers of all the relays. 

Those closed (

positive safety

),  are displayed in bold. With 

 

 and 

 

 key, moves the cursor to 

the desired relay, pressing the 

 

ENTER

 

 button will change its state. To exit, press 

 

ESC

 

This test also checks the output boards. The outputs that are not installed are not displayed.  

 

AUX:

 Check the operation of the Logic Input. Appears on the display its status, i.e., if the contact 

is 

OPEN

 or 

CLOSED

Press 

 

ESC

 

 to return to the previous screen. 

 

SD  CARD: 

checks  the  presence  of  the  memory  card.  The  display  shows  if  the  SD  Card  is 

present

  or 

absent

If  the  SD  Card  was  inserted  and  was  not  detected,  the  card  may  be  not 

properly inserted or the card’s slot is faulty. 

Press 

 

ESC

 

 to return to the previous screen. 

BATTERY (Level 2)

: Pressing 

 

ENTER

 

 on the relevant item, you can choose it, if the battery is installed, 

or manually perform the function test and display the battery voltage. 

 

Then with 

 

 and 

 

 keys, you can choose the item to edit. 

Pressing 

 

ENTER

 

 you can change the value using the 

 

 and 

 

 key. --

 

After choosing the desired  value, press 

 

ENTER

 

 to confirm or press 

 

ESC

 

 to 

go back. 

 
 

The  battery  test is  automatically  performed  every  day.  If  there  is  no  voltage,  the  battery test 
cannot be executed and will be suspended if it is in progress. 

 

The control unit will be automatically powered by the battery, in the event of mains failure. If 
the voltage of the battery falls below 22 VDC, the control unit will automatically shut down 
to  prevent  damage  to  the  battery  (discharging).  When  the  mains  supply  is  present,  the 
battery is charged and kept charged.

 

        SERVICE 

1 ELECTRIC TEST 

 

2 BATTERY 
3 SENSORS STATUS 
4 START-UP 

 ELECTRIC TEST 

1 DISPLAY 

 

2 KEYBOARD 
3 LEDS/BUZZER 
4 OUTPUTS 
5 AUX 
6 SD CARD 

BATTERY 

 
PRES. BATT. 

  NO 

 

TEST BATT 

:  

NO 

 
 
V.BATT. 

27,51 

Содержание City CE408P

Страница 1: ...PA01 02_CE408 EN 02 04 2014 docx Dis 0534045 GAS CONTROL UNIT CITY CE408P USER INSTRUCTIONS GECA S r l Via E Fermi 98 25064 Gussago BS Italy Tel 39 030 3730218 Fax 39 030 3730228 http www cavagnaindu...

Страница 2: ...date of issue In any case must be observed all applicable national regulations in the country of use The information contained in this document is accurate current and are the result of continuous res...

Страница 3: ...23 LOGIC INPUT 23 ENABLE DISABLE Level 1 23 CONFIGURE Level 2 24 DELATE Level 2 25 MODIFY Level 2 25 DETAILS 25 ZONES 25 ENABLE DISABLE Level 1 25 CONFIGURE Level 2 26 DELETE Level 2 27 MODIFY Level 2...

Страница 4: ...eries Should be connecting all models produced up to December 2008 Three wire 4 20mA linear sensors for flammable gas or two wire 4 20mA linear sensors for toxic gases and oxygen Inputs are configurab...

Страница 5: ...seconds of the relay associated with an alarm threshold Hysteresis OFF is the delay adjustable from 0 to 300 seconds of the relay to return to normal condition when it ends the alarm Time ON is adjus...

Страница 6: ...the autonomy 1 hour it can be used two 7Ah batteries connected in series but causes the greatest dimension shall be installed in a case outside the CE408P ELECTRICAL CONNECTIONS The electrical connec...

Страница 7: ...e of those described on the next page Nero Black Noir Rosso Red Rouge AL120 AC DC 27 6V 60W L T N F C B D E A FUSE 2A B B B NC C NO A A Morsetto Ingresso Ausiliario AUX Auxiliary Input Terminal AUX Bo...

Страница 8: ...tacts on the boards indications NA means NO Normally Open NC Normally Closed C Common refer to the relays in the normal position not powered If an output is configured as POSITIVE LOGIC the NO contact...

Страница 9: ...elds Keeping the key pressed increases the speed scrolling ESC Cancel an operation and in the main screen is used to enter to Main Menu LED INDICATIONS The CE408P has 3 LEDs which show the status of u...

Страница 10: ...the last line the battery status of charge if installed and the presence of mains power Symbols used to indicate the status of the battery if installed Full charge Half charge Low charge Discharge Fla...

Страница 11: ...E Fermi 98 25064 GUSSAGO BS Tel 030 3730218 Fax 030 3730228 When a sensor a logic input or a zone activate a relay output the main screen appears a brief display of alarm status This allows to check...

Страница 12: ...ay Pressing the key ENTER again you view the details of the highlighted sensor of course only if it is configured Explanations of the details are as follows 1 st row shows the number of the sensor 2 n...

Страница 13: ...ter a submenu where you can enable disable configure modify copy delete and view the details of the logic input ZONE Enter a submenu where you can enable disable configure modify copy delete and view...

Страница 14: ...r l Via E Fermi 98 25064 GUSSAGO BS Tel 030 3730218 Fax 030 3730228 When performing the RESET with key or from the menu the display shows the confirm message for about 3 seconds then the previous scr...

Страница 15: ...Pressing ENTER on the first line will highlight the number of the sensor Then with and you choose the desired number and pressing ENTER the confirmation window will appear The second line acts on a g...

Страница 16: ...If you have selected a group of sensors the ones that have been configured are enabled or disable Dialog box appears to warn you that you have selected one or more zones are not configured If this pr...

Страница 17: ...of 2 letters followed by 3 numbers and if necessary by other letters 2 to 4 To choose the desired one is followed the same structure must be chosen before the first two letters then 3 numbers and then...

Страница 18: ...e Short Term Exposure Limit is the concentration to which it is believed that workers can be exposed continuously for a short period of time without suffering from irritation chronic or irreversible t...

Страница 19: ...r Manual Pag 19 41 GECA S r l Via E Fermi 98 25064 GUSSAGO BS Tel 030 3730218 Fax 030 3730228 TS220EO TS293EO whose hysteresis is 2 The level of fault FAULT has a hysteresis of 1mA so a sensor failure...

Страница 20: ...y s delay to return to normal status when it ends the alarm condition The second item TIME ON adjustable from 0 to 300 seconds can only be used to stop the alarm output after a preset time even if the...

Страница 21: ...sensor You can choose between LEL Lower Explosive Limit vol Volume ppm parts per million ppb parts per billion and C temperature in degrees Celsius RANGE This item shows the sensor s full scale It con...

Страница 22: ...ns to the beginning of the copy management DELETE Level 2 This item allows you to delete the configuration of a sensor or a group of sensors To delete a sensor press ENTER on the relevant item Using a...

Страница 23: ...if it is different from zero you can press ENTER to view its details The items of the details can be scrolled with and keys In addition at the end of the screen displays the status of silencing outpu...

Страница 24: ...estores the previous value and the entire line is highlighted indicating that you can only scroll through the items The following explains the various items in detail Description of items relating to...

Страница 25: ...ed with and keys In addition at the end of the screen displays the status of silencing output ZONES In this submenu is possible to manage the Zones of the sensors connected to the unit The zones can b...

Страница 26: ...Zone If you have selected a group of Zone the ones that have been configured are enabled or disable Dialog box appears to warn you that you have selected one or more zones are not configured If this...

Страница 27: ...ription is the same as one written in the chapter CONFIGURE SENSORS Please see page 16 OUTPUT N SILENCEABLE SILENCE T DELAY ON DELAY OFF TIME ON POS LOGIC LATCHED At the end of the screen is written C...

Страница 28: ...output EVENTS In this submenu is possible to view the last 100 stored events ALARMS FAULTS are only events related to faults and alarms of the sensors of the inputs outputs and related zones They are...

Страница 29: ...s been switched on MAIN YES Indicates that the unit is powered from the mains if the batteries are installed MAIN NOT Indicates that the unit is powered by batteries only if batteries are installed RE...

Страница 30: ...to confirm The window will inform you that the operation was successful Then the screen returns the beginning of manage Settings If it had been inserted an incorrect date i e 30 02 window will warn yo...

Страница 31: ...NTER on its item Will appear the screen like the one above where you will be asked to enter before the old password and then the new one If the old password entered was wrong the window will warn you...

Страница 32: ...button will change its state To exit press ESC This test also checks the output boards The outputs that are not installed are not displayed AUX Check the operation of the Logic Input Appears on the di...

Страница 33: ...t BAT TEST ON Consider that the two power resistors load will heat up during the test SENSORS STATUS Level 2 This item allows you to view the current value of the sensors connected to the analog input...

Страница 34: ...serted the card and if necessary check its operation using the test see menu Service Electric Test SDCard After the upgrade a message will confirm that the transaction is completed in addition will be...

Страница 35: ...h 8 sensors 3 The batteries are not included If it were required more autonomy can be used 2 Pb Batteries 12V 3Ah or 7Ah connected in series but due to their size they should be installed in an extern...

Страница 36: ...PETROL TS292 KG ST441KG TS293KG SE193 KG GPL TS292KI TS293KI HYDROGEN TS292KM ST441KM TS293KM SE193KM METHANE 0 20 LIE 7 1 10 20 WITH PELLISTOR SENSORS FOR FLAMMABLE GASES Alarm Levels MODELS GAS RANG...

Страница 37: ...ODELS GAS RANGE Unit of measure TWA min Threshold 1 AL1 Threshold 2 AL2 Threshold 3 AL3 TS220EC S TS220EC H TS293EC S TS293EC H CO 0 300 ppm 15 30 60 150 TS220EN TS293EN NO 0 100 ppm 15 10 20 50 TS220...

Страница 38: ...FAULT NO 45 0 0 YES NO SENSORS FOR TOXIC AND ASPHYXIATING GASES CO2 Relay Number ALARM Silenceable Hysteresis ON seconds Hysteresis OFF seconds Time ON seconds Positiv Logic Latched Output 1 AL 1 NO...

Страница 39: ...s Positiv Logic NO YES Latched output 7 NO YES NOTE 1 Only if the Expansion Board ES404 with 4 inputs is installed In each CE408 can be installed one ES404 to obtain a total of 8 Inputs 4 20mA 4 imput...

Страница 40: ...t 2 threshold 1 Relay Number Output 1 threshold 2 Relay Number Output 2 threshold 2 Relay Number Output 1 threshold 3 Relay Number Output 2 threshold 3 Relay Number Output Fault Relay Number ANNOTATIO...

Страница 41: ...IST 1408 PA01 02 Dis 0534045 CE408P User Manual Pag 41 41 GECA S r l Via E Fermi 98 25064 GUSSAGO BS Tel 030 3730218 Fax 030 3730228...

Отзывы: