UNIT’S OPERATION
•
Keyboard:
RESET
Can only be used on the main screen
, it is used to reset the latched outputs to normal
operation, but only if the Sensor or Zone or Input has returned from the alarm condition. If there
are active alarms, outputs configured as
Silenceable
(e.g. alarm) returns to normal operating
conditions only for the time of
silencing
by default.
and
Scroll the display and the numeric digits up and down. Keeping the key pressed,
increases the values' speed scrolling. In the
main screen
changes to display the status of
sensors, inputs and configured zones
MENÙ
Call up the
Main Menu
from any screen.
ENTER
Confirm the inserted data and in the
main screen
allows you to select the detail’s sensors.
and
Scroll through the pages (6 sensors at a time and 7 events at a time), and input fields.
Keeping the key pressed, increases the speed scrolling.
ESC
Cancel an operation and in the
main screen
is used to enter to
Main Menu.
•
LED INDICATIONS
The
CE408P
has 3 LEDs, which show the status of unit operation (
see also Appendix
).
•
FAULT (Yellow LED)
Flashing = Preheat (
Start Unit
) or Firmware
Update.
Fixed ON = Fault (
Sensor
)
+
Buzzer if enabled.
Short flashing = Output relay associated with a latched Fault.
Rapid flashing = Batteries Fault.
•
ON (Green LED)
Fixed ON = Operation with mains power.
Flashing = Operation with the batteries.
•
ALARM (Red LED)
Fixed ON = Alarm 3 is active (
Sensor or Zone
) +
Buzzer if enabled.
Flashing = Alarm 1 and / or 2 active (
sensor or area or logic input
).
Short flashing = alarm latched (indented) (
sensor or area or logic input
).
•
Internal Buzzer Indications
The
CE408
has an internal buzzer that emits a
beep
when a key is pressed. It can also be configured
to sound in the event of a fault and / or an alarm.
•
Sound short (0.1s) is always active
Confirms the pressing of a
key
.
•
Continuous sound if configured
Fault (
Sensor or
Zo
ne)
•
Continuous sound if configured
Alarm 3 is active (Sensor or
Zone)
Keyboard
Fig 5 – CE408P Keyboard
Display
LEDs