Commissioning
Commissioning the control unit
7160-9001-560
01. December 2020
Achieved installation status: S4
1. Repeat installation via service pin
If the status remains S4:
2. Set the installation status manually
(see appropriate section)
3. Check and set section in the Device menu
(see appropriate section)
Achieved installation status: S8
1. Restart the control unit manually (Reboot)
Setting the installation status manually
1. Open user interface
2. Open the section:
Set-up-> System-> Behaviour components-> DPNet
- Settings are displayed
3. Set the installation status to "9" manually
4. Save the setting
Checking and setting the section in the Device menu
1. Check the section in the Device menu (Ad - dS)
2. If necessary, set the section in the Device menu. (Ad - SS)
Recommendation
Check the section on all existing control units, and adjust if necessary.
This prevents conflict when additional control units are subsequently
added.
Recommended section setting:
● DairyRobot / DPQ: 01-09
● CowScout: 10
● AutoSelect (Ethernet): 11-19
● Ethernet-ID: 21-29