12- PID "Limits" and "Out of Range" Mode
Function
Code No.
LCD
Display
Description
Range/Code
Factory
Setting
Remarks
12-0
(Fb Los Det Sel)
Feedback Loss Detection Mode
0000: Disabled
0001: Enabled - Drive Continues to
Operate After Feedback Loss
0002: Enabled - Drive "STOPS"
After Feedback Loss
0000
12-1
(Fb Los Det Lvl)
Feedback Loss Detection Level
(%)
0 - 100
0
12-2
(Fb Los Det Time)
Feedback Loss Detection Delay
Time (Seconds)
0.0 -25.5
1.0
12-3
(PID I Limit)
Integration Limit Value (%)
0 - 109
100
*1
12-4
(I Time value Sel)
Integration Value Resets to Zero
when Feedback Signal Equals
the Intended Value
0000: Disabled
0001: 1 Second
0030: 30 Seconds
0000
12-5
(I Error Margin)
Allowable
Integration
Error
Margin (Units)
(1 Unit = 1/8192)
0 - 100
0
12-6
(PID Comm. Source) PID Feedback signal
0000: 0~10V or
0~20mA
0001: 2~10V or 4~20mA
0000
*7
12-7
(Sleep Level)
Sleep Function Operation Level 0.00-650.00
0.0
12-8
(Sleep Delay Time) Sleep Function Delay Time
0.0-25.5
0.0
13- Communication Mode
Function
Code No.
LCD
Display
Description
Range/Code
Factory
Setting
Remarks
13-0
(Serial Comm Adr)
Assigned Communication
Station Number
1 - 254
1
*2*3
13-1
(Serial Baud Rate) Baud Rate Setting (bps)
0000: 4800
0001: 9600
0002: 19200
0003: 38400
0003
*2*3
13-2
(Comm Stop Bit)
Stop Bit Selection
0000: 1 Stop Bit
0001: 2 Stop Bits
0000
*2*3
13-3
(Comm Parity Sel) Parity Selection
0000: Without Parity
0001: With Even Parity
0002: With Odd Parity
0000
*2*3
13-4
(Comm Data
Format)
Data Format Selection
0000: 8-Bits Data
0001: 7-Bits Data
0000
*2*3