Chapter 4 Software Index
4-10
1-06
(Frequency Source)
Frequency Command Source
Selection
0000: Keypad
0001: Potentiometer on Keypad
0002: External Analog Signal Input
or Remote Potentiometer
0003: Up/Down Frequency
Control Using MFIT (S1 -
S6)
0004: Communication setting
frequency
0005: Inpulse (S5) setting
frequency (ver2.3)
0000
1-07
(Keypad Up/Down)
Keypad Operation with Up/Down
Keys in Run Mode
0000: ‘Enter’ must be pressed after
frequency change with
Up/Down Keys on keypad.
0001: Frequency will be changed
directly when Up/Down
Keys are Pressed
0000
2- Manual/Automatic Restart Modes
Function
Code No.
LCD
Display
Description
Range/Code
Factory
Setting
Remarks
2-00
(PwrL Selection)
Momentary Power Loss and
Restart
0000: Momentary power loss and
restart disable
0001: Momentary power loss and
restart enable
0002: Momentary power loss and
restart enable while CPU is
operating.
(
According to the
capacity of DC power)
0000
2-01
(PwrL Ridethru T)
Momentary Power Loss
Ride-Thru Time (Seconds)
0.0 - 2.0
0.5
2-02
(Delay of Restart)
Auto Restart Delay Time
(Seconds)
0.0 - 800.0
0.0
2-03
(Num of Restart)
Number of Auto Restart
Attempts
0 - 10
0
2-04
(Auto Restart)
Auto Restart Method
0000: Enable Speed Search
0001: Normal Start
0000
2-05
(Direct Start Sel)
Direct Running After Power Up
0000: Enable Direct running after
power up
0001: Disable Direct running after
power up
0001
2-06
(Delay-on Timer)
Delay-ON Timer (Seconds)
0.0-300.0
0.0
2-07
(Reset Mode Sel)
Reset Mode Setting
0000: Enable Reset Only when Run
Command is Off
0001: Enable Reset when Run
Command is On or Off
0000
2-08
(KEB_Decel_Time)
Kinetic Energy Back-up
Deceleration Time
0.0:Disable
0.1~25.0: KEB Deceleration Time