Chapter 4 Software Index
4-39
Parameter Group 6- Jog and Preset (MFIT) Speed Setting on Keypad
Jog and Preset (MFIT) Speed Setting on Keypad
:
:
:
:
6-00~08: Set Jog and preset speed by Keypad
A. 5-00~06=2-4(preset speed 1~3)
The external multifunction terminal = ON, the inverter operates at preset speed. The operation
time of the 8 stages is base on the ON time of the terminal. Please refer to the corresponding
parameters list:
B. 5-00~06=5(Jog terminal)
The external multifunction terminal = ON, the inverter operates in Jog acceleration time/ Jog
decelerate time/ON
Function
Code No.
LCD
Display
Description
Range/Code
6-00
(Keypad Freq)
Keypad Frequency (Hz)
0.00 - 650.00
6-01
(Jog Freq)
Jog Frequency (Hz)
0.00 - 650.00
6-02
(Preset Speed #1)
Preset Speed # 1 (Hz)
0.00 - 650.00
6-03
(Preset Speed #2)
Preset Speed # 2 (Hz)
0.00 - 650.00
6-04
(Preset Speed #3)
Preset Speed # 3 (Hz)
0.00 - 650.00
6-05
(Preset Speed #4)
Preset Speed # 4 (Hz)
0.00 - 650.00
6-06
(Preset Speed #5)
Preset Speed # 5 (Hz)
0.00 - 650.00
6-07
(Preset Speed #6)
Preset Speed # 6 (Hz)
0.00 - 650.00
6-08
(Preset Speed #7)
Preset Speed # 7 (Hz)
0.00 - 650.00
Priority in reading the frequency: Jog > Preset speed > Keypad frequency or external frequency signal
Multifunction
terminal3
Preset value=04
Multifunction
terminal 2
Preset value =03
Multifunction
terminal 1
Preset value =02
Jog Command
terminal
Preset value =05
Output
frequency preset
value
0
0
0
0
6-00
X
X
X
1
6-01
0
0
1
0
6-02
0
1
0
0
6-03
0
1
1
0
6-04
1
0
0
0
6-05
1
0
1
0
6-06
1
1
0
0
6-07
1
1
1
0
6-08
Содержание VAT200
Страница 31: ...Chapter 4 Software Index 4 5 4 1 5 Keypad Operating Example ...
Страница 69: ...Chapter 4 Software Index 4 43 8 02 3 04 frequent detection Fout 8 04 8 02 3 05 over torque detection ...
Страница 88: ...Chapter 4 Software Index 4 62 3 Timer Mode 3 OFF Delay A Mode 4 Timer Mode 4 OFF Delay B Mode ...