Chapter 4 Software Index
4-46
torque is less than the 9-14 setting value.
= 0001
:
If there is over torque, the inverter coasts to stop and flashes OL3. it is necessary to press
‘RESET’ or external terminal to continue to run.
Parameter8-02,03(Multifunction output terminal ) = 05, the output terminal is output over torque signal.
※
Note: Over torque output signal will be output as the parameter 9-12=0001or 0002 when the level and
time are over the range.
Parameter Group 10 – Volts /Hz Pattern Operation Mode
V/F PATTERN Selection
10-0
:
:
:
:
V/F PATTERN Selection = 0 – 18
10-1
:
:
:
:
Torque boost gain(V/F pattern modulation)% = 0.0 – 30.0%
10-2
:
:
:
:
Motor no load current(Amps AC) -------------
10-3
:
:
:
:
Motor rated slip
compensation(%) = 0.0 – 100.0%
10-4
:
:
:
:
Max output frequency(HZ) = 0.20 – 650.0Hz
10-5
:
:
:
:
Max output frequency voltage ratio(%) = 0.0 – 100.0%
10-6
:
:
:
:
Medium frequency(HZ) = 0.10 –650.0Hz
10-7
:
:
:
:
Medium output frequency voltage ratio (%) = 0.0 – 100.0%
10-8
:
:
:
:
Min output frequency(HZ) = 0.10 –650.0Hz
10-9
:
:
:
:
Min output frequency voltage ratio (%) = 0.0 – 100.0%
1. 10-0=18, set the V/F pattern freely complying with 10-4~10-9 (Refer to following diagram)
(V)
%
10-5
(Vmax)
10-7
(Vmid)
10-9
(Vmin)
Hz
10-8 10-6 10-4 650