Chapter 4 Software Index
4-7
4.2 Control Mode Selection
VAT200 Series inverter has three control modes:
1. General Vector Control Mode
2. VT Vector Control Mode (Special for Blower, Pump).
3. V/F Control Mode
。
The user can choose these modes with the digital keypad according to the application characteristics.
The factory setting is general vector control mode. Before operation, please set the control mode and
the relative parameters of the motor in accordance with the following flow chart. (The Vector control
mode only suits for the inverter with same capacity comparing to the motor, or a grade bigger or
smaller one).
※
Note:
1. Use V/F Control Mode:
(1) Use one inverter to drive several motors simultaneously
(2) Motor’s nameplate is unknown
or motor ’s specifications are too special, it will
cause Auto-tuning fault.
(3) Specification of inverter and motor differ more than 1 class.
2. One inverter drives several motors (Only V/F mode available), set the motor parameter complying
with the following rules:
(1). As for the current, sum the rated current of all motors.
(2). As for others, input correct VF Pattern parameter (10-4~10-9).
3. When the nameplate of the motor is unknown, the inverter will set the internal parameter
according to the standard GE motor.
4. When parameter 0-00 does set to 2, the keypad will display ‘Err2’ in performing Auto tuning.
5. When VF control, 0-01~0-05 max. & min. value by the GE standard motor specification limit(one
more & one less level). When VF control, no district.
End
Setting procedure of
control mode
Control mode
V/F
Control
Control mode selection
0-00=2
Set the following parameter:
V/F Pattern 10-0
Torque Boost 10-1
Motor no load current 10-2
(<=0-02)
Motor Rated Slip 10-3
Max output frequency 10-4
Max output voltage 10-5
Medium output Frequency 10-6
Medium output voltage 10-7
Min output frequency 10-8
Min output voltage
10-9
Suitable motor capacity 0-02 (OL1 reference index)
Set the following parameter:
Motor rated voltage 0-01
Motor rated current 0-02
Motor power 0-03
Motor rated Speed 0-04
Motor rated Frequency 0
-05
Power Voltage 0-07
Vector Control
Perform Auto tuning (0-06=1)
Control mode selection
0-00=0
0-00=1