5–6
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
QUICK SETUP MENU
CHAPTER 5: QUICK SETUP - FRONT CONTROL PANEL
GND IOC FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
GND CT INPUT
Range: CT(W1), CT(W2)
Default: CT(W1)
GND IOC1 PICKUP
Range: 0.05 to 20.00 x CT in steps of 0.01 x CT
Default: 1.00 x CT
RLY1 TRIP W1 BKR
Range: Do not operate, Operate
Default: Do not operate
RLY2 TRIP W2 BKR
Range: Do not operate, Operate
Default: Do not operate
NOTE
NOTE:
The settings changed using the Quick Setup menu, are available for review and
modification by navigating through
S2 SYSTEM SETUP
and
S3 PROTECTION > SETPOINT
GROUP 1
in the
SETPOINTS
main menu.
menu are available for rew