Chapter 2. CPU Features & Specifications
GFK-2222AD
April 2018
33
CPU310
CPU315
CPU320/
CRU320
17
CPE302
18
/
CPE305
CPE310
CPE330
CPE400
Protocols
Modbus RTU Slave
Y
Y
Y
Y
Y
N/A
N/A
SNP Slave
Y
Y
Y
Y
Y
N/A
N/A
Serial I/O
Y
Y
Y
Y
Y
N/A
Y
31
SRTP (# simultaneous server conns)
up to 32
up to 32
up to 48
up to 48
Modbus TCP
(# simultaneous server connections)
up to 16
32
up to 16
up to 16
up to 16
SRTP Channel or Modbus TCP Client
(# simultaneous)
up to 16
up to 16
up to 32
up to 32
Ethernet Global Data (EGD)
FW 8.30
FW 8.30
FW 8.60
Y
Number of EGD Exchanges (max)
34
255
255
255
255
Selective Consumption of EGD
Y
Y
Y
Y
PROFINET
35
N
N
FW 8.90
Y
OPC-UA Server
36
FW 8.20
FW 8.20
Remote Station Manager over UDP
Y
Y
Y - limited
Y - limited
Station Manager over Serial Comm Port
via ETM001
via ETM001
via ETM001
via ETM001
via ETM001
via ETM001
N/A
31
CPE400 Serial IO requires firmware version 9.40 or later.
32
Sixteen clients are permitted: each may be SRTP or Modbus/TCP.
33
EGD Class 1 only: supports up to 255 simultaneous Class 1 EGD exchanges.
34
Limit is per target, so all producers and consumers in the CPU system are counted towards this limit.
35
CPE400 and CPE330 (firmware version 8.90 or later) provide PROFINET support via an embedded PROFINET Controller: no external hardware is required. All other CPUs that
support PROFINET require a rack-mounted PROFINET Controller (IC695PNC001). CPE330 may also host IC695PNC001 modules in the CPU rack. Refer to the
PACSystems RX3i
PROFINET IO-Controller Manual
, GFK-2571F or later.
36
For a discussion of OPC UA, refer to
PACSystems RX7i & RX3i TCP/IP Ethernet Communications User Manual,
GFK-2224M Chapter 10.
37
Supports up to 5 concurrent sessions with up to 10 concurrent variable subscriptions and up to 12,500 Variables.