Chapter 2. CPU Features & Specifications
22
PACSystems* RX7i, RX3i and RSTi-EP CPU Reference Manual
GFK-2222AD
The Embedded PROFINET Controller may be configured as a Simplex PROFINET IO-Controller with
support for up to 32 I/O devices. For update rates, loading and other considerations, refer to the
PACSystems RX3i PROFINET IO Controller User Manual,
GFK-2571F or later.
The Embedded PROFINET Controller supports Media Redundancy Protocol (MRP) and may be used as
either a Media Redundancy Manager (MRM) or Media Redundancy Client (MRC) on a redundant media
ring. For details concerning the Media Redundancy Protocol, refer to the
PACSystems RX3i PROFINET IO
Controller User Manual,
GFK-2571F or later.
The following CPUs support Hot Standby Redundancy with PROFINET IO, using the embedded PROFINET
Controller (LAN2):
•
CPE330 with firmware version 9.40 or later. The PROFINET Controller may be the embedded
PROFINET Controller or a rack-mounted IC695PNC001.
•
CPE400 with firmware version 9.30. The PROFINET Controller is always the embedded PROFINET
Controller.
For embedded PROFINET Controllers, this feature permits control of up to 32 devices, 20 of which may
be redundant. For rack-mounted IC695PNC001, this feature permits control of up to 128 devices, all of
which may be redundant.
Note that the host PLC CPU can support up to 255 redundant devices, which may be allocated across 2,
3, or 4 PROFINET Controllers (any combination of embedded PROFINET Controller and/or PNC001
modules).
2.1.7
OPC UA
Each PACSystems CPE302/CPE305/CPE310/CPE330/CPE400 and RSTi-EP CPE100/CPE115 supports
Open Productivity and Connectivity Unified Architecture (OPC UA) Server communications on the
embedded Ethernet port only.
For more information on OPC UA support refer to
PACSystems RX7i, RX3i and RSTi-EP TCP/IP Ethernet
Communications User Manual,
GFK-2224 version M or higher (Chapter 10).
Note:
Effective with CPE310/CPE305 firmware version 8.20, or CPE302 firmware version 9.40, the
CPE embedded Ethernet port supports OPC UA Server.
Effective with CPE310/CPE305 firmware version 9.20, or CPE330 firmware version 9.21, or
CPE302 firmware version 9.40, OPC UA Server is configurable through Proficy Machine Edition
15
.
15
Proficy™ Machine Edition Logic Developer PLC 9.00 SIM 10, or 9.50 SIM 2, or later is required for
OPC UA Server
configuration.