Page 20
Segment 4
â
On if Fail To Communicate report enabled.
ã
On if Log Full report enabled.
ä
On if Autotest report enabled.
å
On if Start/End programming report enabled.
æ
On if End Download report enabled.
ç
On if Sensor Low Battery report enabled.
è
On if Sensor Missing report enabled.
é
Reserved.
Segment 5
â
On enable Lost Clock service light.
ã
On enables Zone Doubling for zones 7 -12 (requires NX-200 Zone Doubling Kit).
ä
On disables on-board zones.
å
On will allow two trips on same cross-zone to activate an alarm.
æ
On will
not
allow zones that are force armed to report bypass.
ç
Reserved
è
Use internal crystal for clock.
é
Disable Temporal Siren on Fire. (
Note: Must not be disabled for UL listed systems.
)
Refer to the feature definitions beginning on page 3.
LOCATION 38
SWINGER SHUTDOWN COUNT
Location 38 contains the number of trips on a zone before that zone is bypassed automatically.
Refer to the feature
definitions beginning on page 3.
Factory default is 1.
LOCATION 39
KEYPAD SOUNDER CONTROL
1 segment, feature selection
â
On if keypad sounds for
A
Telephone Line Cut
@
when the system is armed.
ã
On if keypad sounds for
A
Telephone Line Cut
@
when disarmed.
ä
On if keypad sounds upon AC Power Failure.
å
On if keypad sounds when a Low Battery is detected.
æ
On if keypad sounds during Cross Zone trip time.
ç
On if keypad sounds for zone and box tampers.
è
Reserved.
é
On if keypad sounds for expander trouble (required for UL installations).
LOCATION 40
SYSTEM TIMERS
10 segments, numerical data
Location 40 contains the duration of various system timing functions. Example: If you desire the duration of the
Dynamic Battery Test to be 30 minutes, you should program [3]-[0]-[
r
] in segment 1 of this location. The [3]-[0] is the
number of minutes, and the [
r
] stores the data and moves to the next segment of this location.
SEGMENT DESCRIPTION SELECTIONS
DEFAULT
NOTES
1
Dynamic Battery Test
duration
0 - 255 minutes
0
"0" = no test
The "Dynamic Battery Test" feature cannot
exceed 4 hours for UL residential fire
installations.
2
AC Fail report delay
0 - 255 minutes
5
0 = no delay
3
Power Up delay
0 - 60 seconds
60
0 = no delay
4
Siren time
1 - 254 minutes
8
5
Telephone Line Cut delay
0 - 255 seconds
0
0 = no TLM
6
Cross Zone time
0 - 255 minutes
5
0 = no Cross Zoning
7
Chime time in 50 mS
(1/20th second) increments
0 - 255 mS
3
255 mS = 12 seconds
0 follows zone, 255 is latched
8
Dial delay
15 - 255 seconds
30
The "Dial Delay" feature shall be set to –0- for
UL Listed systems. Must be disabled by zone
type in Loc 110-169.
The combined Dial Delay and Entry Delay (loc
24) must not exceed 1 minute fro SIA CP-01
requirements.
9
Fire Alarm Verification time
120 - 255
seconds
0
0= no Fire Alarm Verification
This feature is not approved for residential
use in California.
10
Listen-In time
0 - 255 seconds
0
0 = no Listen-In time
The "Listen-In" feature cannot be enabled for
UL Listed systems.