Setpoints, Pg. 7
3 SETUP AND USE
3-37
7
ENABLE U/V TRIP & ALARM
ENABLE U/V TRIP & ALARM
IF AVG. VOLTS=0? XXX
IF AVG. VOLTS=0? XXX
This setpoint should be used if an undervoltage alarm or trip is desired on a dead bus, i.e. when the av-
erage voltage of all three phases is zero.
YES - Enables undervoltage trip & alarm features if the average voltage received from the meter is zero.
Reset of an U/V trip or alarm is only possible if the average voltage goes above the setpoints.
NO - If the bus is de-energized (or dead), the 269 will not issue an undervoltage trip or alarm. In fact, if
an undervoltage trip or alarm condition existed prior to the average voltage becoming zero, these
conditions may be reset after the average voltage becomes zero.
8
UNDERVOLTAGE ALARM LEVEL
UNDERVOLTAGE ALARM LEVEL
U/V ALARM = XX %VT
U/V ALARM = XX %VT
This setpoint sets the threshold for the undervoltage alarm condition as a percentage of VT primary.
The alarm level programmed in this setpoint is compared to the average voltage received from the me-
ter.
NOTE: To detect an undervoltage alarm upon complete loss of all three phases, the setpoint "Enable U/V
Trip & Alarm if Avg. Volts=0?" must be set to Yes.
30-95 % (increments of 1) or OFF
Factory Value = OFF
9
U/V ALARM TIME DELAY
U/V ALARM TIME DELAY
TIME DELAY = XXX SEC
TIME DELAY = XXX SEC
This setpoint sets the time that an undervoltage alarm condition must persist in order to facilitate an
alarm.
1-255 seconds (increments of 1)
Factory Value = 10
10
UNDERVOLTAGE TRIP LEVEL
UNDERVOLTAGE TRIP LEVEL
U/V TRIP = XX %VT
U/V TRIP = XX %VT
This setpoint sets the threshold for the undervoltage trip condition as a percentage of VT primary.
The alarm level programmed in this setpoint is compared to the average voltage received from the me-
ter.
NOTE: To detect an undervoltage trip upon complete loss of all three phases, the setpoint "Enable U/V
Trip & Alarm if Avg. Volts=0?" must be set to Yes.
30-95 % (increments of 1) or OFF
Factory Value = OFF
11
U/V TRIP TIME DELAY
U/V TRIP TIME DELAY
TIME DELAY = XXX SEC
TIME DELAY = XXX SEC
This setpoint sets the time that an undervoltage trip condition must persist in order to facilitate a trip.
1-255 seconds (increments of 1)
Factory Value = 5
Содержание MULTILIN 269 MOTOR MANAGEMENT RELAY Series
Страница 3: ...TABLE OF CONTENTS ii GLOSSARY ...
Страница 11: ...2 INSTALLATION 2 2 Figure 2 2a Phase CT Dimensions ...
Страница 12: ...2 INSTALLATION 2 3 Figure 2 2b Ground CT 50 0 025 3 and 5 window ...
Страница 13: ...2 INSTALLATION 2 4 Figure 2 2c Ground CT 50 0 025 8 window ...
Страница 14: ...2 INSTALLATION 2 5 Figure 2 2d Ground CT x 5 Dimensions ...
Страница 17: ...2 INSTALLATION 2 8 Figure 2 4 Relay Wiring Diagram AC Control Power ...
Страница 19: ...2 INSTALLATION 2 10 Figure 2 6 Relay Wiring Diagram Two Phase CTs ...
Страница 20: ...2 INSTALLATION 2 11 Figure 2 7 Relay Wiring Diagram DC Control Power ...
Страница 29: ...2 INSTALLATION 2 20 Figure 2 11 269 Drawout Relay Physical Dimensions ...
Страница 30: ...2 INSTALLATION 2 21 Figure 2 12 269 Drawout Relay Mounting ...
Страница 31: ...2 INSTALLATION 2 22 Figure 2 13 269 Drawout Relay Typical Wiring Diagram ...
Страница 34: ...2 INSTALLATION 2 25 Figure 2 16 MPM Mounting Dimensions ...
Страница 35: ...2 INSTALLATION 2 26 Figure 2 17 MPM to 269 Typical Wiring 4 wire Wye 3 VTs ...
Страница 36: ...2 INSTALLATION 2 27 Figure 2 18 MPM to 269 Typical Wiring 4 wire Wye 2 VTs ...
Страница 37: ...2 INSTALLATION 2 28 Figure 2 19 MPM to 269 Typical Wiring 3 wire Delta 2 VTs ...
Страница 38: ...2 INSTALLATION 2 29 Figure 2 20 MPM to 269 Typical Wiring 2 CT ...
Страница 39: ...2 INSTALLATION 2 30 Figure 2 21 MPM Wiring Open Delta ...
Страница 40: ...3 SETUP AND USE 3 1 Figure 3 1 Front Panel Controls and Indicators ...
Страница 74: ...Setpoints Pg 6 3 SETUP AND USE 3 35 13 END OF PAGE SIX END OF PAGE SIX SETPOINT VALUES SETPOINT VALUES ...
Страница 86: ...3 SETUP AND USE 3 47 Figure 3 2 Wiring Diagram for Contactors ...
Страница 87: ...3 SETUP AND USE 3 48 Figure 3 3 Wiring Diagram for Breakers ...
Страница 93: ...3 SETUP AND USE 3 54 Figure 3 5 Standard Overload Curves ...
Страница 102: ...4 RELAY TESTING 4 2 Figure 4 1 Secondary Injection Test Set AC Input to 269 Relay ...
Страница 103: ...4 RELAY TESTING 4 3 Figure 4 2 Secondary Injection Test Set DC Input to 269 Relay ...
Страница 106: ...4 RELAY TESTING 4 6 Figure 4 3 Hi Pot Testing ...
Страница 108: ...5 THEORY OF OPERATION 5 2 Figure 5 1 Hardware Block Diagram ...
Страница 110: ...5 THEORY OF OPERATION 5 4 Figure 5 2 Firmware Block Diagram ...
Страница 112: ...6 APPLICATION EXAMPLES 6 2 Figure 6 1 Thermal Limit Curves ...
Страница 126: ...APPENDIX H H 3 Figure H 1 Excitation Curves Figure H 2 Excitation Curves Method ...
Страница 133: ......
Страница 137: ......
Страница 139: ......
Страница 141: ......
Страница 142: ......