GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
155
Electrical Specifications,
Continued
AC Current Inputs (42x Nominal)
Nominal CT Input Options
1 A
rms
or
5 A
rms
DFR Range
42x nominal
Measurement Range
2% to 1600% of nominal, asymmetrical
Thermal Overload
4 times nominal current continuous
30 times nominal current 10 seconds
100 times nominal current 1 second
Note
:
continuous over-current may affect the
accuracy of the current values.
Refer to the appropriate PRPI for the accuracy
specifications under over-current conditions.
Burden
Less than 0.1 VA @ nominal input current
LCD Display
Operating temp.
-20 to 70 degrees Celsius
LCD Display size
2.75” x 7.4”
AC Voltage Inputs
Nominal PT input options
63.5 V
rms
69.3 V
rms
110 V
rms
120 V
rms
220 V
rms
Measurement Range
0% to 250% of nominal
Overload Voltage
250% of nominal continuous
350% of nominal for one (1) minute
Burden
Less than 0.1 VA
AC Current Inputs (Standard)
Nominal CT Input Options
1 A
rms
5 A
rms
Measurement and DFR Range
2% to 1600% of nominal, asymmetrical
Thermal Overload
4 times nominal current continuous
30 times nominal current 10 seconds
100 times nominal current 1 second
Note
:
continuous over-current may affect the
accuracy of the current values.
Refer to the appropriate PRPI for the accuracy
specifications under over-current conditions.
Burden
Less than 0.1 VA @ nominal input current
Содержание D25
Страница 170: ......