GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
101
Downloading a Configuration,
Continued
Prerequisites
for Serial Code
Download
The following must be available before a FLASH code file can be loaded into
a D25’s FLASH memory:
•
Windows PC with terminal emulation communication software loaded.
•
The code file, in the Motorola S-record format, located on a local hard drive. If
the file is located on a network or floppy drive, the download may be
significantly slower.
−
This file typically will be named either:
down.shx, or
sal
xxxx
.shx
•
A WESMAINT cable to connect the PC to the D25’s WESMAINT port.
Before Starting
•
This procedure will suspend all operation of the D25, and following the
download, the unit will probably require a configuration download before it
becomes operational.
•
Consult your System Administrator for access and authorization to perform
system download procedures.
•
In Application Monitor, (i.e., when the
D25A>
prompt is displayed)
configuration files can be downloaded — but code cannot be downloaded.
•
To download code, System Monitor (i.e., when the
D25S>
prompt is displayed)
must be running.
Procedure:
Download files
Steps to download a firmware file to the D25’s FLASH memory
Step
Action
Access Application Monitor
1
Connect the WESMAINT serial cable from PC to the D25’s
WESMAINT port
2
Start terminal emulation communication software on the PC, and
configure it as follows:
−
9600 Bps
−
8 bit
−
no parity
−
VT100 emulation
−
Xon/Xoff (software) flow control enabled
Note
If the D25 has no code file loaded, or it has detected a corrupt FLASH file,
you will have to go directly to Step 8 and log directly into the monitor.
Содержание D25