D25
User's Manual
GE Grid Solutions
92
994-0081-3.00-21
GE Information
Testing Hardware I/O Points,
Continued
Note
Only points used by the Plant I/O, based on downloaded configuration, will
display values.
Unused points will be off-line.
Table:
Reference
Values
Use this table as example references for the AC analog input verification test.
Note
: Nominal values can be determined by reviewing SGConfig’s P097
Plant I/O configuration tables for this device.
Point Description
Nominal Value
Voltage Phase A Circuit 1
13107
Voltage Phase B Circuit 1
13107
Voltage Phase C Circuit 1
13107
Current Phase A Circuit 1
2048
Current Phase B Circuit 1
2048
Current Phase C Circuit 1
2048
Neutral Current Circuit 1
2048
Voltage Phase A-B Circuit 2
13107
Voltage Phase B-C Circuit 2
13107
Current Phase A-B Circuit 2
2048
Current Phase B-C Circuit 2
2048
Neutral Current Circuit 2
2048
Notes
•
Full-scale for all AC analog values displayed in WESMAINT is represented by a
count of 32767 (15-bit plus sign value).
•
Full-scale of voltage measurements is 2.5 times the nominal value.
•
Full-scale of current measurements is 16 times the nominal value.
•
For more detailed information, refer to the
D25 Plant I/O Subsystem
Configuration Guide
.
Содержание D25
Страница 170: ......