GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
33
Connecting Field Wiring
This Section
Use this section to:
•
Make all field wiring connections
•
Set external jumper configurations
•
Configure Serial and Ethernet ports
Power Supply
Power Supply
A label on the back panel outlines the actual power connection points for the
Power Supply option installed.
Term # 1 2 3 4 5
-- Wetting
+ Wetting
+/L
-- /N
Aux.
Ground
+ Wetting
Supply Output
24V or +48V according to the power supply option specified.
- Wetting
Supply Output
Either -24V or -48V according to the power supply option specified.
+/L Input
•
Positive if using DC power supply
•
Line if AC power supply
-/N Input
•
Negative if DC power supply
•
Neutral if AC power supply
!
Grounding
Connect the protective ground stud before operating the D25. Tighten the
ground stud to a torque value between 4.2 to 5.0 in-lb [0.475 to 0.565 Nm]
Use the ground stud for shielding.
External
Overcurrent
Protection
The D25 power supply input must be externally protected:
•
AC mains supplies shall be fused at no more than 15A, or
•
DC mains supplies shall be fused at no more than 10A