GE Grid Solutions
D25
User's Manual
GE Information
994-0081-3.00-21
79
Configuring the D25 to work with a DNP3 I/O Module
, continued
Example
Configuration
For example, when configuring your D25 RTU Master to work with a DNP
Digital Input Module, assume that you have a DNP Digital Input Module:
• That is factory-configured with 64 digital inputs
• That has DNP address 0032
• Which is to be polled every 500 ms.
• With every poll, we want a full status update.
To meet these requirements, you would configure the DNP DCA as shown in
the below table:
Table
Parameter
Value
Remote Device Table
Application Address
0032
Remote Device Point
Mapping Table
DCA Object Type
Binary Input
Number of Device Points
64
Remote Device Polling Table Poll Data Type
Integrity
Poll Interval
500 ms