CHAPTER 5: CONFIGURING THE SOFTWARE
D20MX INSTRUCTION MANUAL
GE INFORMATION
75
2.
Open the project containing the configuration of the target D20MX device.
Result: The project's Main Page appears.
3.
Click on the D20MX device.
Result: The Communications group appears in the ribbon.
4.
Change the communication options to enable LAN communication with the D20MX.
Click the SGConfig ribbon Configure group > Communications > Options.
Result: The D2x Device Communication Options dialog box opens.
5.
Click the Interface tab the in the Connection Type group select iSCS LAN, then select
the Preferred LAN you wish to use, either LAN A or LAN B. This will most likely be LAN A.
Result: The iSCS LAN option is selected.
6.
Click OK to close the D2x Device Communication Options dialog box
Result: The dialog box is closed and the SGConfig ribbon
Configure
group >
Communications
>
Firmware
transfer pick list is now active.
7.
Click the
Configure
group >
Communications
>
Firmware
transfer >
HSP transfer
.
Result: A dialog displaying a warning appears.
8.
Read the warning then click Yes to continue or No to abort the operation.
Result: If Yes is selected, then refer to the following table. If No is selected, the
operation is aborted.
9.
Ensure the
Standby IP
checkbox is checked and if not, check it. In the associated
IP
address
field, ensure the IP address of the standby unit
address
is displayed and if
not, enter it.
TIP
Click
Help
for information on how to determine the Standby IP address.
10. Click
OK
.
Result: A login dialog appears.
11. Enter the
User Name
and
Password
of an account having SHELL access level of
Maintenance or higher and click
Login
.
Result: The
Login
dialog box closes, and the
Transferring HSP
dialog box opens. The
HSP transfer takes place. When the transfer is complete, the
Transferring HSP
dialog
box closes, and the
HSP Transferred successfully
dialog box opens.
12. Click
OK
to close the HSP Transferred successfully dialog box.
Result: The dialog box closes.
Apply HSP
1.
Start SGConfig.
Result: The Welcome to SGConfig screen appears.
2.
Open the project containing the configuration of the target D20MX device.
Result: The project's Main Page appears.
3.
Change the communication options to enable serial communication with the D20MX.
3.1.
Click the SGConfig ribbon
Configure
group >
Communications
>
Options
.
Result: The D2x Device Communication Options dialog box opens.
Possible Result if Yes is Selected
When to expect this result
Go to step
Select Target IP Address dialog
appears
If the D20MX is configured for device
redundancy
step 10
Login dialog appears
If the D20MX is configured for standalone
operation
step 12
Содержание D20MX
Страница 1: ...GE Digital Energy GE Information D20MX Processor Instruction Manual 994 0140 Version 1 4x Revision 1 ...
Страница 10: ...10 GE INFORMATION D20MX INSTRUCTION MANUAL ABOUT THIS DOCUMENT ...
Страница 32: ...32 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Страница 90: ...90 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 5 CONFIGURING THE SOFTWARE ...
Страница 112: ...112 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX B STANDARDS PROTECTION ...
Страница 116: ...116 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX C FREQUENTLY ASKED QUESTIONS ...
Страница 148: ...148 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX D USING CONFIGPRO WITH D20MX ...
Страница 158: ...158 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX E SECURE CONNECTION FOR LOGICLINX ...
Страница 162: ...162 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX F LIST OF ACRONYMS ...
Страница 168: ...168 GE INFORMATION D20MX INSTRUCTION MANUAL INDEX ...