CHAPTER 3: CONNECTING TO DEVICES AND NETWORKS
D20MX INSTRUCTION MANUAL
GE INFORMATION
43
General cabling requirements
Table 12 lists the cables required to connect to the D20MX:
Table 12: Connection cables
To provide higher EMC immunity and maintain CE Mark radiated emission compliance, the
serial cables used for permanent serial and D.20 Link connections must comply with the
following requirements:
•
Cables must be shielded
•
D-type connector covers must provide EMC shielding (e.g. metallized plastic or die cast
metal covers).
Serial
Seven serial communications ports are brought out to the backplane connector P2. These
serial ports are five-signal (TXD, RXD, RTS#, CTS#, DCD#) DTE serial ports, compliant to
ANSI/TIA-232 and TIA/EIA-694 specifications and are hosted by UARTs.
The D20MX is tested with all 7 serial ports running at 19200 baud with 20% CPU utilization.
Refer to application configuration guides for supported baud rates and for data bits.
To avoid burning out the WESTERM or D20MX mainboard when directly connecting a rear-
panel serial port on one D20MX chassis to another rear-panel serial port on any type of
D20 chassis, jumper the WESTERM of both chassis' to not provide a power connection to
pin 4. Refer to the appropriate WESTERM module layout for jumper settings.
D.20 Link
Communications between the D20 and the D20 peripheral I/O modules are carried over a
high-speed, high-level data link control (HDLC) protocol called the D.20 Link. The D.20 Link
has the following features:
•
RS-485 serial link, half duplex, 250 kbps
•
D.20 frame using HDLC protocol format with Manchester encoding
•
Supports up to 38 D20 I/O peripheral modules in a standard configuration
Media
Designation
Cabling
Connector
Serial
RS-232
Shielded
DB-9 female
D.20 Link
RS-485
2 wire
Shielded
DB-9 female
Twisted Pair Ethernet
(GE part number 526-3001 only)
10/100/1000BASE-T UTP (Unshielded Twisted
Pair) – CAT 5 or better
RJ-45
Fiber optic
(GE part number 526-3003 and
526-3005LF only)
100BASE-FX
1300 nm, 50/125
μ
m and
62.5/125
μ
m multimode
duplex fiber cable
ST-style
connectors
Содержание D20MX
Страница 1: ...GE Digital Energy GE Information D20MX Processor Instruction Manual 994 0140 Version 1 4x Revision 1 ...
Страница 10: ...10 GE INFORMATION D20MX INSTRUCTION MANUAL ABOUT THIS DOCUMENT ...
Страница 32: ...32 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Страница 90: ...90 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 5 CONFIGURING THE SOFTWARE ...
Страница 112: ...112 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX B STANDARDS PROTECTION ...
Страница 116: ...116 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX C FREQUENTLY ASKED QUESTIONS ...
Страница 148: ...148 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX D USING CONFIGPRO WITH D20MX ...
Страница 158: ...158 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX E SECURE CONNECTION FOR LOGICLINX ...
Страница 162: ...162 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX F LIST OF ACRONYMS ...
Страница 168: ...168 GE INFORMATION D20MX INSTRUCTION MANUAL INDEX ...