APPENDIX B: STANDARDS & PROTECTION
Table 70: Safety publications
Table 71: Environmental standards
IEC 61000-4-6
IEC 60255-22-6
IEC 61850-3: clause 5.7.1.1
Immunity to conducted disturbances,
induced by radio-frequency fields
150 kHz to 80 MHz: 10Vrms
IEC 60255-22-1
1 MHz burst immunity test
IEC 61000-4-8
Power frequency magnetic field
immunity test
IEC 61000-4-9
Pulse magnetic field immunity test
IEC 61000-4-12
Ring wave
IEC 61000-4-11
Voltage dips, short interruptions and
voltage variations immunity tests
IEC 61000-4-16
IEC 61850-3: clause 5.7.1.3
Test for immunity to conducted, common
mode disturbances in the frequency
range 0 Hz to 150 kHz
30Vrms, 300Vrms
IEC 61000-4-17
Ripple on DC input power port immunity
test
IEC 61000-4-29+
Voltage dips, short interruptions and
voltage variations on DC input power
port immunity test
This standard only applies when using
high voltage DC as the source (100 V DC
to300 V DC).
Standard Name
Description
Test Specification
IEC 61010-1
Safety requirements for electrical
equipment for measurement, control and
laboratory use - General requirements
IEC 60255-5
Insulation coordination for measuring
relays and protection equipment-
Requirements and tests
Dielectric and Resistance
measurements not applicable
due to design (TVS in circuit)
Standard Name
Description
Test Specification
IEC 60068-2-1
Cold
144 hours powered at - 20 °C
IEC 60068-2-2
Dry Heat
144 hours powered at + 70 °C
IEC 60068-2-6
Vibration (sinusoidal)
A logarithmic sweep from 10 Hz to
150 Hz to 10 Hz at 1 oct/min for 1
sweep cycle in the 3 orthogonal axes.
Acceleration level 1 g
IEC 600255-21-2
Shock - Operating Response Test
Shock - Non-Operating Withstand
Test
Pulse shape: Half sine Pulse duration:
11 mS
- Operating Response Test:
Acceleration level: 5 g's
- Non-Operating Withstand Test:
Acceleration level: 15 g's
3 pulses per polarity per axis for a total
of 18 pulses
IEC 600255-21-2
Bump – Non operating test
Pulse shape: Half sine Pulse duration:
16 mS Acceleration level: 10 g's
1000 pulses per polarity per axis for a
total of 6000 pulses
IEC 60068-2-30
Damp heat, cyclic (12 h + 12 h
cycle)
Standard Name
Description
Test Specification
Содержание D20MX
Страница 1: ...GE Digital Energy GE Information D20MX Processor Instruction Manual 994 0140 Version 1 4x Revision 1 ...
Страница 10: ...10 GE INFORMATION D20MX INSTRUCTION MANUAL ABOUT THIS DOCUMENT ...
Страница 32: ...32 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Страница 90: ...90 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 5 CONFIGURING THE SOFTWARE ...
Страница 112: ...112 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX B STANDARDS PROTECTION ...
Страница 116: ...116 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX C FREQUENTLY ASKED QUESTIONS ...
Страница 148: ...148 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX D USING CONFIGPRO WITH D20MX ...
Страница 158: ...158 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX E SECURE CONNECTION FOR LOGICLINX ...
Страница 162: ...162 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX F LIST OF ACRONYMS ...
Страница 168: ...168 GE INFORMATION D20MX INSTRUCTION MANUAL INDEX ...