![GE D20MX Скачать руководство пользователя страница 67](http://html.mh-extra.com/html/ge/d20mx/d20mx_instruction-manual_122958067.webp)
CHAPTER 5: CONFIGURING THE SOFTWARE
D20MX INSTRUCTION MANUAL
GE INFORMATION
67
NOTE
In the event that you have selected dialog checkbox “Do not show this message again”,
some of the following steps do not appear. Accordingly, ignore the affected steps.
1.
Connect Ethernet port 1 of the D20MX to the Ethernet switch using the appropriate
Ethernet patch cable.
2.
Connect the PC's network adapter to the Ethernet switch using the appropriate
Ethernet patch cable.
3.
Start SGConfig.
Result: The Welcome to SGConfig screen appears.
4.
Open a project containing the target D20MX device.
Result: The project's Main Page appears.
5.
Click on the D20MX device.
Result: The Communications group appears in the ribbon.
6.
Click
Configure
ribbon group >
Communications
>
Options
.
Result: D2x Device Communication Options dialog appears
7.
Click
Interface
tab > Connection Type >
iSCS LAN
and select the Preferred LAN you
wish to use, either
LAN A
or
LAN B
. This is most likely to be
LAN A
.
8.
Click
OK
.
Result: D2x Device Communication Options dialog closes.
9.
Click
Edit
ribbon group >
Properties
.
Result: The D20MX Device Wizard appears
10. Click
Next
.
Result: The Project LAN properties appear.
11. Click
Next
.
Result: The hardware and other properties appear for the device.
12. Click
Processor
tab >
Code Image
sub-tab.
13. Click the button with the ellipsis (
…
).
Result: The Select Flash image file dialog appears.
14. Navigate to the folder containing the appl.out file and vxWorks file.
15. Select the
appl.out
file and click
Open
.
Result: The full pathname of the appl.out file appears in the Flash Image File box.
Note
: To transfer the operating system image, simply ensure that a vxWorks file exists
in the same folder as the selected appl.out file. SGConfig automatically transfers both
files to the D20MX even though you only selected the appl.out file.
16. Click
Next
.
17. Click
Finish
.
Result: The project's Main Page appears with the D20MX device selected.
18. Click the ribbon
Configure
group >
Configuration
>
Generate
.
19. Confirm that there are zero errors in the Device Log.
20. Click the ribbon
Communications
group >
Firmware transfer
.
Result: Warning message appears and confirmation to continue is requested.
21. Acknowledge the warning and click
Yes
to continue or
No
to abort the operation.
Содержание D20MX
Страница 1: ...GE Digital Energy GE Information D20MX Processor Instruction Manual 994 0140 Version 1 4x Revision 1 ...
Страница 10: ...10 GE INFORMATION D20MX INSTRUCTION MANUAL ABOUT THIS DOCUMENT ...
Страница 32: ...32 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Страница 90: ...90 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 5 CONFIGURING THE SOFTWARE ...
Страница 112: ...112 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX B STANDARDS PROTECTION ...
Страница 116: ...116 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX C FREQUENTLY ASKED QUESTIONS ...
Страница 148: ...148 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX D USING CONFIGPRO WITH D20MX ...
Страница 158: ...158 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX E SECURE CONNECTION FOR LOGICLINX ...
Страница 162: ...162 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX F LIST OF ACRONYMS ...
Страница 168: ...168 GE INFORMATION D20MX INSTRUCTION MANUAL INDEX ...