52
GE INFORMATION
D20MX INSTRUCTION MANUAL
CHAPTER 3: CONNECTING TO DEVICES AND NETWORKS
Figure 21: RS-232 Switch panel
A pair of LEDs marked
CCU A
and
CCU B
indicate which of the D20 units is currently active.
If the hardware or software of the active unit fails, it is automatically switched offline and
serial connections to the field are transferred to the standby unit. A toggle switch on the
RS-232 switch panel can be used to switch the D20 devices between active and standby
modes.
Failover sequence
If the active D20 unit fails, the following actions occur:
1.
The standby D20 unit detects the failure through the lack of a heartbeat signal on the
ping cable or through a status change on the watchdog cable.
2.
The standby D20 unit attempts to pull the RS-232 switch panel to assume the active
state.
3.
The RS-232 switch panel transfers all serial field connections to the standby D20,
which then becomes the active D20.
Required components
To implement a redundant D20 system, you need the components: listed in Table 20.
Table 20: Redundant D20 system - required components
NOTE
Pins 4 on switch panel connectors J2 through J9 are tied together and to the panel’s power
supply. Any loading from field devices on these pins, loads the RS-232 panel power supply
and should be taken into consideration when sizing power supplies.
Active/Standby Sw itch
Power Indicator LEDs
CCU Indicator LEDs
CCU A
CCU B
PWR A
PWR B
Component
Function
Part Number
RS-232 Switch Panel
Communications switch.
517-0247
Power Supply
Power supply to power the RS-232 switch panel.
Input: 85 – 264 V AC or 90 – 350 V DC.
580-0046
Watchdog Cable
Assembly
Connects D20 A to the RS-232 switch panel.
977-0160
Connects D20 B to the RS-232 switch panel.
977-0160
Ping Cable Assembly
Links both D20 units to facilitate a heartbeat message
that determines the status of the active unit.
977-0122
RS-232 Serial Cable
Connects the D20 to the RS-232 switch panel which is
then connected to external field devices.
977-0121
Power/SysFail Cable
Connects the RS-232 switch panel to D20 external power
supply.
970-0161
Ground Cable
Provides a ground connection for the RS-232 switch panel. 970-0182
Содержание D20MX
Страница 1: ...GE Digital Energy GE Information D20MX Processor Instruction Manual 994 0140 Version 1 4x Revision 1 ...
Страница 10: ...10 GE INFORMATION D20MX INSTRUCTION MANUAL ABOUT THIS DOCUMENT ...
Страница 32: ...32 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Страница 90: ...90 GE INFORMATION D20MX INSTRUCTION MANUAL CHAPTER 5 CONFIGURING THE SOFTWARE ...
Страница 112: ...112 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX B STANDARDS PROTECTION ...
Страница 116: ...116 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX C FREQUENTLY ASKED QUESTIONS ...
Страница 148: ...148 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX D USING CONFIGPRO WITH D20MX ...
Страница 158: ...158 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX E SECURE CONNECTION FOR LOGICLINX ...
Страница 162: ...162 GE INFORMATION D20MX INSTRUCTION MANUAL APPENDIX F LIST OF ACRONYMS ...