23.3 Recorder Output Options
To set the recorder output, remove all jumpers from headers W8A, W8B, W9A, W9C, W9D,
W10A-C, W11A, W11B. Install jumpers as specified in the following table.
Recorder Output Options
Recorder Output
+4 to +20 mA *
+1 to +5 Vdc
0 to -10 Vdc
Jumper Settings
W8A, W9C,
W10A, W11A
W8B, W9D,
W10B, W11B
W8B, W9A, W9C,
W10A, W10C,
W11B
* Standard Configuration as shipped from factory.
23.4 Gap Full Scale Range Options
To set the gap full-scale range option, remove jumpers W12B-D, W12G. Install jumpers
specified in the following table.
Gap Full Scale Range Options
Gap Full Scale Range
Install Jumpers
0 - 19 Vdc *
(All transducers)
NJ
15 - 0 - 15 mils
(7200 5 & 8mm, 3300 8mm, RAM, 3300XL 8mm and 3000)
W12D **
25 - 0 - 25 mils
(7200 5 & 8 & 11 & 14mm, 3300 8mm, 16mm HTPS, 3300 XL
11mm, and 3300XL 8mm)
W12C**
50 - 0 - 50 mils
(7200 11 & 14mm, 3300 16mm HTPS, 3300 XL 11mm)
W12C, D**
300 - 0 – 300 um
(7200 5 & 8mm, 3300 8mm, RAM, 3300XL 8mm and 3000)
W12B**
600 - 0 – 600 um
(7200 5 & 8 & 11 & 14mm, 3300 8mm, 16mm HTPS, 3300 XL
11mm, and 3300XL 8mm)
W12B, D**
1000 - 0 - 1000 um
(7200 11 & 14mm, 3300 16mm HTPS, 3300 XL 11mm)
W12B, C**
* Standard Configuration as shipped from factory.
** If external barriers are used with this gap full-scale range, install jumper W12G also.