Section 14 - Channel Bypass
25
14. Danger Bypass
You can use Danger Bypass to bypass the DANGER Relay. The
DANGER
alarm LEDs on
the front panel can come on but the DANGER Relay drive will not be activated if a Danger
setpoint is exceeded.
1. Set
DB
to the left (ON) to Bypass the Danger Relay.
•
For the Danger Bypass (
DB
) switch to function, the Danger Bypass Enable jumper
must be installed. See Monitor Options,
Section 10
, for more information.
2. Both
BYPASS
LEDs come on. The
OK
LEDs will remain on as long as the transducer
remains within its OK range.
NOTE
Channel alarms are cleared when Channel Bypass is switched on.
Caution
Machine protection provided by
this monitor will be lost while
Danger Bypass is on.