3300/16 Dual Vibration Monitor Operation Manual
22
12. Alarm Setpoint Adjustment
12.1 Alert and Danger Setpoint Adjustment
1. Open front panel.
2. Set the adjust channel A switch
(
AA
) to the left (ON). The left
(Channel A) bargraph will start
flashing the channel A vibration
signal.
3. Press and hold the
ALERT
or
DANGER
switch on the front
panel. Use the outer meter scale.
4. Press the (
↑
) or (
↓
) switches on
the System Monitor to adjust the
setpoint level up or down.
Caution
Changing Alarm Setpoints
will change the trip levels of
the machine.