3300/16 Dual Vibration Monitor Operation Manual
40
Recall stored error codes by using the
User-invoked self-test. Use the
following steps to run the User-
invoked self-test, read error codes,
and clear stored error codes:
NOTE:
User-invoked self-test cannot
be initiated if any error is active.
Refer to the Error Codes section for
more information on the error codes.
1. Initiate the User-invoked self-test by shorting the two self-test pins (
ST
) with a
screwdriver. All the LEDs and LCD elements
will come on for 5 seconds.
2. If an active or stored error is present at the
end of the self test, the
BYPASS
LEDs remain
on, the
OK
LEDs flash at 5 Hz, and the first
error code flashes at 2 Hz.
•
The error code is given by the number of
flashing segments in one column of the
bargraph.
For example, this monitor is indicating error code
number 6.
Caution
Machine protection will be lost
during calibration and for the
duration of the self-test.