Section 19 - Self Test
41
3.
Read any other stored
error codes by pressing and
holding the
ALERT
switch for
approximately one second.
For example, the display to the far
right contains a second stored
error code - number 10.
•
When you reach the end of the
error code list, the LCD
bargraph comes on at full
scale range and the
OK
LEDs
turn off.
•
You may read through the list
again by continuing to press
the
ALERT
switch.
3. When the LCD bargraph is at
full scale, clear error codes
from memory by pressing and
holding the
DANGER
switch for
approximately one second.
4. If Timed OK/Channel Defeat is
selected, after you clear the
error codes (and after the 30-
second Timed OK/Channel
Defeat period elapse), the
OK
LEDs will flash at 1 Hz to
indicate that the monitor has
been NotOK.