3. Control Terminals
1
2
3
4
5
6
7
8
9
12
13
14
15
16
18
19
BU-
External braking
unit (optional)
Strip X1
F unction
max
Programmable / configurable analog differential input. Signal: terminal 1.
Reference point: terminal 2. Default setting: Ramp ref 1
±
10V
Programmable / configurable analog differential input. Signal: terminal 3.
@ 0.25mA
Reference point: terminal 4. Default setting: none
(20 mA when
Programmable / configurable analog differential input. Signal: terminal 5.
current ref
input)
Reference point: terminal 6. Default setting: none. (1)
+10VDC
Reference v10V; Reference point: terminal 9
+10V/10 mA
-10VDC
Reference voltage -10V ; Reference point: terminal 9
-10V/10 mA
0V
Internal 0V and reference point for
±
10V
-
Enable drive
Drive enable: 0V or open; drive disabled; +15…+30V: Drive enabled
+30V
Start
Drive start command: 0V or open: No start; +15…+30V: Start
3.2 mA@15V
F ast stop
OV or open: Fast stop. +15…+30V; No Fast stop.
5 mA@24V
External fault
OV or open: External fault. +15…+30V; No External fault
6.4 mA@30V
COMD I/O
Reference point for digital inputs and outputs, term.12...15, 36...39, 41...42
-
0V24
Reference point for +24V OUT supply, terminal 19
-
+24VDC
+24V supply output. Reference points: terminals 18 or 27 or 28
+22…28V
120 mA@24V
Analog input 1
Analog input 2
Analog input 3
Analog output
1
Program. analog output; def. setting: Motor speed. Ref. point: term. 22
±
10V/5 mA
0V
Internal 0V and reference point for terminals 21 and 23
-
Analog output
2
Program. analog output; def. setting: Motor current. Ref. point: term. 22
±
10V/5 mA
BU comm.
output
VeCon controlled BU-... braking units command. Ref. point: term. 27.
+28V/15 mA
0V24
Reference point for BU-...command ,terminal 26
-
RESERVED
-
Digital input1
+30V
Digital input2
3.2 mA@15V
Digital input3
5 mA@24V
Digital input4
6.4 mA@30V
Digital output
1
+30V/40 mA
Digitaloutput
2
Supply DO
Supply input for digital outputs on terminals 41/42. Ref. point: term.16.
+30V/80 mA
Motor PTC
1.5mA
Programmable digital output; default setting: none
Motor PTC sensing for overtemperature (cutoff R1k if used)
Programmable digital input; default setting: none
21
22
23
26
27
28
29
36
37
38
39
41
42
46
78
79
R1K
Strip X2
F unction
max curr.
250VAC
1A, AC11
250VAC
1A, AC11
OK relay
contact
Potential-relay contact configurable (relay2).
Default: open 0 drive stopped
R elay 2
contact
Potential-relay contact OK relay (closed=OK)
80
82
83
85
RESERVED