22

9. Options

Encoder verification:

 Set the Drive in V/f mode and run

the motor, enable and start the drive and set an analog
reference.  If the reference is positive on terminal 1 with
respect to 2 (common) the motor should be turning
clockwise.  With the motor turning clockwise (looking at
the drive end), monitor the encoder measurement by
selecting “Monitor/measurements/speed/speed in rpm/
Enc 1 speed”.  The speed should be positive, not negative.
If it is negative, then A and A- or B and B- should be
interchanged on the encoder.  Now return to the “Set Up
for Running” section.

Current Limit:

  The current limit will have been set to

approximately 136% by default in the previous setup (exact
number is a function of the power factor but the difference
is very small).  The value actually set can be verified by
(from “Basic Menu”) pressing down/right arrow to “Limits”,
then 

[Enter]

, then down/right arrow to “current limits”, then

[Enter]

, then down right arrow to “T current lim” and 

[Enter]

.

The value of T current limit can be changed to a higher (or
lower) number.  Bear in mind that the ultimate limits are
based on the capacity of the drive, not the motor.  T current
is the torque producing component of total current.  Settings
in excess of 200% are possible, although the motor may
not be able to handle this current.  Current Limit restricts
the magnitude of the torque current reference. The drive
has other alarms and faults to provide motor and drive
current protection.

I/O Configuration:

  This drive can be configured in several

ways.

The standard drive has three standard analog inputs and
two analog outputs as well as six digital inputs and two
digital outputs. These are assignable and configurable.  

The

drive is defaulted already to provide the analog outputs
as Actual speed and Torque current

. To set up the drive

for two analog outputs (one for speed and one for load)
for metering or other purposes, do the following:

Refer to the “Control terminals” section of this guide
showing a description of the connections to the regulator.
A more detailed description and discussion of the I/O are
shown in the manual. The analog outputs are defaulted to
a scale of 1, which means 10 volts out at the max parameter
value. In other words, if analog output 1 is set to max speed
then max speed will be scaled to 10 VDC (maximum output
voltage available) at “Speed Base Value”. If you wanted 5
volts out at max speed then set the scale to 0.5.  If the
output were set to Torque current then 10 VDC would be
rated current.  If you wanted the output to be 10 Vdc at
150% of “Full Load Current” then the scale would be 0.66.
The standard factory default is already set up for speed
(with scale factor of 1) on analog output 1 (terminals 21
and 22) and load (Torque current, with scale factor of 1) on
analog output 2 (terminals 23 and 22).  Note that terminal

22 is a common for both the outputs.  This common can
be grounded, and should be grounded somewhere,
preferably at the load device (meter).

How to disable analog input 1 as ramp  reference:

Analog inputs 2 and 3 are defaulted to off, #1 is defaulted
to Ramp ref 1.

Press 

[Up arrow]

/

[Down arrow]

 to “I/O Config”, then

[Enter]

.

Press 

[Down arrow]

 to “Analog inputs”, then 

[Enter]

for Analog input 1, then 

[Enter]

 to Select input 1, then

[Enter]

 to display the setting, which will be “Ramp ref

1”.

Press 

[Up arrow]

 / 

[Down arrow]

 keys  until “OFF” is

displayed, then 

[Enter]

.

How to enable analog input 2 as ramp reference

Press 

[Up arrow]

/

[Down arrow]

 to “I/O Config” and

press 

[Enter]

, then down right arrow to “analog inputs”

then 

[Enter]

 for “analog input 1” then 

[Down arrow]

to ”analog input 2. Then 

[Enter]

 to “select input 2”;

then 

[Enter]

 again to see the set up.  It says “OFF”.

Use the 

[Up arrow]

 / 

[Down arrow]

  keys to display

“Ramp ref 1” and 

[Enter]

.  This means the analog input

2 (terminals 3 and 4) will be the ramped (accel/decel)
speed reference for the drive.

The manual shows the entire configuration of other
I/O in the drive.

10. Quick Tuning Guide for Factory
Configured (or pre-configured)
Drives

When the drive configuration has already been set and
you are simply fine tuning the drive you can ignore most of
the preceding procedure. It is recommended that you go
through the steps anyway, if the data is suspect.  You can
just use the 

[Left arrow]

 key rather than the 

[Enter]

 key in

all the steps in which the entry is found to be correct.  Start
with step 4 of the full procedure and 

do not default the

parameters to factory parameters

. If there is any

question about whether the existing setup should be saved
or not, then use the configuration tool software that came
with the drive and save the file to a PC first so it can be
used later.

Содержание AV-300i

Страница 1: ...1 GE Industrial Systems AV 300i AV 300i Quick Start Up Guide TM...

Страница 2: ...ot covered sufficiently for the purchaser s purpose the matter should be referred to GE Industrial Systems This document contains proprietary information of General Electric Company USA and is furnish...

Страница 3: ...11 5 1 Encoder type connection 11 5 2 JUMPERS setting 12 List of jumpers and dip switch 12 List of dip switch 13 5 3 Maximum cable length for encoder terminals 13 6 Keypad operation 14 Keypads on righ...

Страница 4: ...ut provoquer des incendies ou des explosions Les drives doivent tre install s loin des z nes dangeureuses et quip s de moteurs appropri s WARNING STRAIN HAZARD ATTENTION L L VATION Improper lifting pr...

Страница 5: ...AUTION The drive must be mounted on a wall that is constructed of heat resistant material While the drive is operating the temperature of the drive s cooling fins can rise to a temperature of 194 F 90...

Страница 6: ...ales et nationales Le moteur doit tre prot g contre la surcharge 9 No dielectric tests should be carried out on parts of the drive A suitable measuring instrument internal resistance of at least 10 k...

Страница 7: ...anel ACDrive AC Line Reactor Ground Bus Motor cable terminals AC Motor Encoder cable EMI filter U1V1W1 U2V2W2PE2 PE1 AC Voltage Contactor AC fuses Note PE1 is the drive safety ground If PE2 is used to...

Страница 8: ...e enabled with those 2 Overview This guide assumes a standard start up using the keypad for a drive and motor that is to be run in either sensorless vector or flux vector with digital or sinusoidal en...

Страница 9: ...9 41 42 0V24 Reference point for 24V OUT supply terminal 19 24VDC 24V supply output Reference points terminals 18 or 27 or 28 22 28V 120 mA 24V Analog input 1 Analog input 2 Analog input 3 Analog outp...

Страница 10: ...tput current AC line voltage 480 VAC 10 3Ph See table 2 4 2 1 Motor connection AC line volt 3Ph 1 36 X output current Braking resistor optional M 3Ph PE1 Grounding protective earth conductor U1 L1 V1...

Страница 11: ...ital or 10 mA digital or For E digital commutation or SIN absolute position signal 1V pp analog 8 3 mA analog Channel F 5V digital or 10 mA digital or For F digital commutation or COS absolute positio...

Страница 12: ...Termination resistor IN OFF Noterminationresistor S8 Adaptation of the input signal of analog input 1 terminals 1 and 2 OFF ON 0 20mA 4 20mA OFF 0 10V 10 10V S9 Adaptation of the input signal of anal...

Страница 13: ...FF ON OFF ON OFF ON OFF ON OFF S2 OFF ON ON OFF OFF ON ON OFF OFF ON S3 ON ON ON OFF OFF OFF OFF ON ON ON S4 OFF OFF OFF ON ON ON ON ON ON ON S5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF S6 OFF OFF OFF...

Страница 14: ...eypad is used To control the drive when keypad use has been programmed Main commands DIGITAL To display the speed voltage diagnostics etc during operation To set parameters LEDs The LEDs present on th...

Страница 15: ...tion Rotation control changes the direction in Jog mode and Motor pot mode when the shift button is selected Down arrow Used to change menu or parameter selection In parameter and reference setting mo...

Страница 16: ...16 Moving inside a menu...

Страница 17: ...Relay 2 83 85 and regulation board points 1 46 XS XE connections Regulator Terminal Board Inputs 12 ENABLE DRIVE close to activate 13 START close to activate 14 FAST STOP open to cause a stop 15 EXTE...

Страница 18: ...elect 400 6 Set Actual Motor Data Press Left arrow until back to Drive parameter then Enter to get Mot plate data and Enter to Nominal Voltage then Enter again to see the value Using the Up arrow Down...

Страница 19: ...to the enable disable functions 11 Save Parameters Press Left arrow to limits then Up arrow until Basic Menu then Enter then Down arrow to save parameters then Enter The display will read wait until t...

Страница 20: ...This procedure is not suitable for use with hoist or elevator drives Encoder feedback is required when Field oriented mode is selected Set the current limit BASIC MENU T Current lim to a value compati...

Страница 21: ...ot to disable Enable motor pot parameter Disable if you will want to use an analog voltage on terminal 1 for speed reference Jog function Note This function is enabled as a default setting Enable jog...

Страница 22: ...other words if analog output 1 is set to max speed then max speed will be scaled to 10 VDC maximum output voltage available at Speed Base Value If you wanted 5 volts out at max speed then set the scal...

Страница 23: ...inal flux Nominal voltage Nom frequency and working flux Base voltage base frequency is too high Verify the above parameters value The Magnetizing current 165 value is too high Verify that this value...

Страница 24: ...gains Try to repeat the self tune procedure to eliminate accidental measurement errors If this error persist do not use the Take val part 3 command The speed regulator will probably be stable with th...

Страница 25: ...and 19 If the External fault message is displayed The signal on terminal 15 is missing 15 30 V to terminal 16 With an external voltage supply commons must be connected together Failure supply Fault i...

Страница 26: ...unit to increase the energy absorption capability Overtemp Motor Overtemperature of the motor indicated via thermistor on terminals 78 79 Cable between thermistor in motor and terminals 78 and 79 int...

Страница 27: ...heck configuration of the reg terminals Drive not accepting commands incorrect or wrong operating mode Protective device ahead of the power supply has tripped protective device incorrectly sized or in...

Страница 28: ...ence value Zero Minimum speed parameter selected Interference due to unused analog input Remedy set unused analog inputs to OFF Disconnect reference on the analog input If drive now stands still the e...

Страница 29: ...to an analog input Motor potentiometer function not executed Function not enabled Enable motor pot Enabled With operation via the terminal strip Motor pot up and or Motor pot down and Motor pot sign...

Страница 30: ...GEK 105661 5M 5 99 GE Industrial Systems 1501 Roanoke Boulevard Suite 435 Salem VA 24153 1 800 543 6196 www GEindustrial com...

Отзывы: