NOTE:

“xxx range error” or “timeout” messages may also occur in
some extreme parameter ranges. Repeat the tune in this
case. If error messages are persistent see troubleshooting
section.

If there was some reason you did not want to keep these
values permanently, but only wanted to try to run the drive
with them, there is no need to save them to permanent
memory.  If power is cycled however, these values will be
lost unless the “Save Parameter” function is used.

14. Self tune part 3:

The third part of self tuning  (Speed regulator tuning)
identifies the total inertia at the motor shaft, the friction
value and computes the proportional and integral gains
of the speed regulator. The motor needs to be free to
turn with load attached to the shaft.

NOTE:

When regulation mode = field-oriented, the encoder needs
to be verified before running Self Tune 3. Refer to page 22
“Encoder Verification”. After this verification procedure, put
the regulation mode back to field oriented.

WARNING !

This procedure requires free rotation of the motor shaft
coupled to the load. The Start/Stop command is
ignored, therefore it can not be used on drives with
limited travel, or when free rotation presen ts a safety
problem.

CAUTION !

The test is performed using the torque limit value set
in Test T curr lim parameter. The torque is applied in a
step fashion, with no ramp profile. Therefore, the
mechanical transmission must not have significant
backlash, and it must be compatible with operation at
the torque limit set in the Test T curr lim parameter.
The user can reduce the torque limit to a suitable value
via the Test T curr lim parameter.

Note !

• Application where the system inertia coupled to the

motor shaft is much higher than the motor inertia value
, increase the Test T curr lim parameter to avoid “Time
out” error.

• This procedure is not suitable for use with “hoist”

or “elevator” drives.

• Encoder feedback is required when Field oriented mode

is selected.

• Set the current limit (BASIC MENU\ T Current lim +/-)

to a value compatible with the motor size and load.
(Example when motor is 1/3 of the Drive power, the
limit should be reduced compared to the default value).

• Select the torque current value to be used during the

test via the 

Test T curr lim 

parameter

Now press 

[Left arrow]

 to see “self tune 2a or 2b”

then 

[Down arrow]

 to “self tune 3” and press 

[Enter]

to Fwd-Rev spd tune, then 

[Enter]

. Set the motor shaft

direction for this test: Forward or Reverse by using

[Up arrow]

 / 

[Down arrow]

  keys. Press 

[Enter]

 to

set the selection.

Enable the drive using a switch on terminal 12 [and
close terminal 13 to terminal 19 if Speed control
function is enabled (default)].  Press 

[Down arrow]

to “Start part 3” then press 

[Enter]

,  “start part 3 ?”

then 

[Enter]

 and see “measure speed” will appear and

the motor will turn.  Wait until the display says “end”,
press 

[Left arrow]

 to see “self tune 3” then 

[Enter]

and press 

[Down arrow]

 to see “take val part 3”.

Disable the drive, then 

[Enter]

.  You are now finished

with the initial set up and tuning with values stored in
only in the “working memory”.

NOTE:

“xxx range error” or “timeout” messages may also occur
in some extreme parameter ranges. Repeat the tune in
this case. If error messages are persistent see
troubleshooting section.

NOTE:

If there was some reason you did not want to keep these
values permanently, but only wanted to try to run the drive
with them, there is no need to save to permanent memory.
If power is cycled however, these values will be lost unless
the next step is taken.

To save all values to permanent memory, select 

Save

parameters 

and press 

[Enter]

 .

15.Set up for Running:

First, before saving, let’s put the drive into the
configuration you want to run it in.

The drive is factory setting to run through the Increase

[+]

 and Decrease 

[-]

 keys (

Enable motor pot

parameter 

= Enabled), see the following instruction to

run.

Содержание AV-300i

Страница 1: ...1 GE Industrial Systems AV 300i AV 300i Quick Start Up Guide TM...

Страница 2: ...ot covered sufficiently for the purchaser s purpose the matter should be referred to GE Industrial Systems This document contains proprietary information of General Electric Company USA and is furnish...

Страница 3: ...11 5 1 Encoder type connection 11 5 2 JUMPERS setting 12 List of jumpers and dip switch 12 List of dip switch 13 5 3 Maximum cable length for encoder terminals 13 6 Keypad operation 14 Keypads on righ...

Страница 4: ...ut provoquer des incendies ou des explosions Les drives doivent tre install s loin des z nes dangeureuses et quip s de moteurs appropri s WARNING STRAIN HAZARD ATTENTION L L VATION Improper lifting pr...

Страница 5: ...AUTION The drive must be mounted on a wall that is constructed of heat resistant material While the drive is operating the temperature of the drive s cooling fins can rise to a temperature of 194 F 90...

Страница 6: ...ales et nationales Le moteur doit tre prot g contre la surcharge 9 No dielectric tests should be carried out on parts of the drive A suitable measuring instrument internal resistance of at least 10 k...

Страница 7: ...anel ACDrive AC Line Reactor Ground Bus Motor cable terminals AC Motor Encoder cable EMI filter U1V1W1 U2V2W2PE2 PE1 AC Voltage Contactor AC fuses Note PE1 is the drive safety ground If PE2 is used to...

Страница 8: ...e enabled with those 2 Overview This guide assumes a standard start up using the keypad for a drive and motor that is to be run in either sensorless vector or flux vector with digital or sinusoidal en...

Страница 9: ...9 41 42 0V24 Reference point for 24V OUT supply terminal 19 24VDC 24V supply output Reference points terminals 18 or 27 or 28 22 28V 120 mA 24V Analog input 1 Analog input 2 Analog input 3 Analog outp...

Страница 10: ...tput current AC line voltage 480 VAC 10 3Ph See table 2 4 2 1 Motor connection AC line volt 3Ph 1 36 X output current Braking resistor optional M 3Ph PE1 Grounding protective earth conductor U1 L1 V1...

Страница 11: ...ital or 10 mA digital or For E digital commutation or SIN absolute position signal 1V pp analog 8 3 mA analog Channel F 5V digital or 10 mA digital or For F digital commutation or COS absolute positio...

Страница 12: ...Termination resistor IN OFF Noterminationresistor S8 Adaptation of the input signal of analog input 1 terminals 1 and 2 OFF ON 0 20mA 4 20mA OFF 0 10V 10 10V S9 Adaptation of the input signal of anal...

Страница 13: ...FF ON OFF ON OFF ON OFF ON OFF S2 OFF ON ON OFF OFF ON ON OFF OFF ON S3 ON ON ON OFF OFF OFF OFF ON ON ON S4 OFF OFF OFF ON ON ON ON ON ON ON S5 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF S6 OFF OFF OFF...

Страница 14: ...eypad is used To control the drive when keypad use has been programmed Main commands DIGITAL To display the speed voltage diagnostics etc during operation To set parameters LEDs The LEDs present on th...

Страница 15: ...tion Rotation control changes the direction in Jog mode and Motor pot mode when the shift button is selected Down arrow Used to change menu or parameter selection In parameter and reference setting mo...

Страница 16: ...16 Moving inside a menu...

Страница 17: ...Relay 2 83 85 and regulation board points 1 46 XS XE connections Regulator Terminal Board Inputs 12 ENABLE DRIVE close to activate 13 START close to activate 14 FAST STOP open to cause a stop 15 EXTE...

Страница 18: ...elect 400 6 Set Actual Motor Data Press Left arrow until back to Drive parameter then Enter to get Mot plate data and Enter to Nominal Voltage then Enter again to see the value Using the Up arrow Down...

Страница 19: ...to the enable disable functions 11 Save Parameters Press Left arrow to limits then Up arrow until Basic Menu then Enter then Down arrow to save parameters then Enter The display will read wait until t...

Страница 20: ...This procedure is not suitable for use with hoist or elevator drives Encoder feedback is required when Field oriented mode is selected Set the current limit BASIC MENU T Current lim to a value compati...

Страница 21: ...ot to disable Enable motor pot parameter Disable if you will want to use an analog voltage on terminal 1 for speed reference Jog function Note This function is enabled as a default setting Enable jog...

Страница 22: ...other words if analog output 1 is set to max speed then max speed will be scaled to 10 VDC maximum output voltage available at Speed Base Value If you wanted 5 volts out at max speed then set the scal...

Страница 23: ...inal flux Nominal voltage Nom frequency and working flux Base voltage base frequency is too high Verify the above parameters value The Magnetizing current 165 value is too high Verify that this value...

Страница 24: ...gains Try to repeat the self tune procedure to eliminate accidental measurement errors If this error persist do not use the Take val part 3 command The speed regulator will probably be stable with th...

Страница 25: ...and 19 If the External fault message is displayed The signal on terminal 15 is missing 15 30 V to terminal 16 With an external voltage supply commons must be connected together Failure supply Fault i...

Страница 26: ...unit to increase the energy absorption capability Overtemp Motor Overtemperature of the motor indicated via thermistor on terminals 78 79 Cable between thermistor in motor and terminals 78 and 79 int...

Страница 27: ...heck configuration of the reg terminals Drive not accepting commands incorrect or wrong operating mode Protective device ahead of the power supply has tripped protective device incorrectly sized or in...

Страница 28: ...ence value Zero Minimum speed parameter selected Interference due to unused analog input Remedy set unused analog inputs to OFF Disconnect reference on the analog input If drive now stands still the e...

Страница 29: ...to an analog input Motor potentiometer function not executed Function not enabled Enable motor pot Enabled With operation via the terminal strip Motor pot up and or Motor pot down and Motor pot sign...

Страница 30: ...GEK 105661 5M 5 99 GE Industrial Systems 1501 Roanoke Boulevard Suite 435 Salem VA 24153 1 800 543 6196 www GEindustrial com...

Отзывы: