AV-300i Version 2 User’s Guide
—————— Function Description ——————
Ch.1
49
V out
f
SAVE ENERGY
SE flux ramp time
SE cmd src
SE flux level src
1.4.3.3 V/f Catch on Fly from Running on AC Input
The function allows the Drive to catch an already rotating motor, “Autocapture”.
An automatic restart of the Drive is possible after a “Retrying” temporary alarm condition.
Through the V/f catch cmd src source it is possible to select the origin of the command signal enabling the function.
In the configurations the function can be parameterized according to the application.
REGULATION PARAM
V/f reg param
V/f catch on fly
V/f catch src
V/f catch cmd
V/f catch cfg
Spd search time
Vlt search time
Catch init speed
Catch demag dly
Catch retry dly
V/f catch src
V/f catch cmd
Source of the command starting the catch procedure (see List 3)
V/f catch cfg
Spd search time
It states the change of the Drive output frequency. It shows the
time needed to perform a frequency change from zero to the motor
rated one if the output current is equal to the motor rated one.
Vlt search time
It states the machine flux change. It shows the time needed to
perform a flux change from zero to the motor rated one, if the
output current is equal to the motor rated one.
Catch init speed
It states the starting speed for the synchronism search.
Catch demag dly
Delay time for the motor demagnetization before performing the
synchronism search (in case the “autocapture” function is present).
Catch retry dly
Delay time for the motor demagnetization (with the “retrying”
function).
Содержание AV-300i
Страница 1: ...GEH 6641E Supersedes GEH 6641D GE Industrial Systems AV 300i TM Version 2 User s Guide ...
Страница 2: ......
Страница 12: ...GEH 6641E TABLE OF CONTENTS 12 ...
Страница 44: ...GEH 6641E Function Description 44 Ch 1 ...
Страница 174: ...GEH 6641E Function Description 174 Ch 1 ...
Страница 295: ......