46
—
⑤
Drainage Pipe
1 Installing Drainage Pipe
●
The diameter of drainage pipe shall be equal to or larger than the diameter of the connecting pipe (size of
polyethylene pipe : outer diameter 25mm, wall
≥①
1.5mm)
●
The drainage pipe shall be short, with a declining slop as at least 1/100, so as to avoid the forming of gaseous
envelope.
●
In case it is impossible to have enough slope for the flexible drainage pipe, install a drainage lift pipe.
●
To avoid bending of the flexible drainage pipe, the distance between the two suspenders shall be 1 to 1.5m.
(Correct) Slope more than 1/100 (Wrong)
●
Use the flexible drainage pipe
①
and the clamp
②
supplied as accessories with the unit
●
Insert the flexible drainage pipe into the drainage faucet, and then tighten the clamp
②
.
●
Use the big sponge
⑩
to wrap the clamp at the flexible drainage clamp for thermal insulation.
●
Take thermal insulation measures for the indoor flexible drainage pipe.
2 Precautions for Installing Drainage Lift Pipe
●
The installation height of drainage lift pipe shall be less than 280mm.
●
The drainage lift pipe shall be perpendicular to the unit and no more than 300mm from the unit.
Note : The gradient of accessory flexible drainage pipe
①
shall be within 75mm, so that the drainage faucet does not
subject to extra external force.
ST-Joint Confluent Drainage Pipe
Above 100mm
3. After installation is completed, check if the water can be drained smoothly.
●
Fill in 600cc water from the outlet or the check hole slowly to check the draining conditions.
●
After the electrical lines are installed, check the draining conditions in the cooling operation.
Clamp
②
Sponge (Gray)
Flexible Drainage Pipe
①
Big Sponge
⑩
(Accessory)
Clamp
②
(Accessory)
Below 4mm
Roof
Within 300
Suspending Frame Base
Below 280mm
Flexible Drainage
Tube
①
(accessory)
Drainage Lift Pipe
Ceiling
Clamp
②
(accessory)
Содержание AIR C18
Страница 2: ......
Страница 3: ......
Страница 5: ... 2 Model Remarks GE AIR C24 Communication Ceiling Mounted Unit 1PH 230V 50Hz R407C ...
Страница 14: ... 11 Applicable to GE AIR C24 OUT Unit mm Over 600 Bolt Nut Wrench ...
Страница 15: ... 12 Applicable to GE AIR C34 C41 OUT 378 Unit mm Over 600 Bolt Nut Wrench ...
Страница 17: ... 14 Electrical Diagram GE AIR C18 GE AIR C24 6 ...