CS875-575-375-275-175 Installers Manual with CS5500 keypad
C.1.4
Control
Fail to Comm.
The control panel tried to send a message to the
central station but failed.
Ensure that the phone line is connected properly. Use a test
phone to check that the phone service is available. Ensure that
the central station phone number, account and protocol options
are correct.
Control
Loss of Time
The control panel has had a total loss of power and
the clock must be reset.
Reset the system clock and date.
Control
Low Battery
The standby battery for the control panel is low.
The battery may need replacing. This may be a temporary
condition caused by a long power failure.
Control
Over-Current
The control panel has detected an excessive amount
of current being drawn from one of the outputs and
has disabled the output as a means of protection.
Check the system for wiring faults.
An overcurrent message can be reset only by triggering the siren
correctly, for example, by generating a tamper on a zone that
activates the sirens. This is a security feature to ensure that the
overcurrent message has disappeared and the sirens can work
properly again.
Control
Phone Trouble
The phone line connected to the control panel is not
working properly.
Ensure that the phone line is connected properly. Use a test
phone to check proper service.
Control
Power Trouble
The mains power supply to the control panel is
missing.
Reconnect the power supply and ensure it is working properly.
Control
Siren Trouble
The connection to the control panel’s siren is broken.
Repair the open circuit.
Expansion
Aux. Comm. Fail
A reporting module tried to send a message to the
central station but failed.
Ensure that the phone line is connected properly. Use a test
phone to check that the phone service is available. Ensure that
the central station phone number, account and protocol options
are correct. Check that the module is connected and working.
Expansion
Box Tamper
There has been interference with the casing of an
expansion module.
Ensure that the casing is not damaged and is mounted correctly
on a flat surface. If there is no damage, close the casing
securely.
Expansion
Low Battery
The standby battery in an expansion module is low.
The battery may need replacing. This may be a temporary
condition caused by a long power failure.
Expansion
Over-Current
The expansion module has detected an excessive
amount of current being drawn from one of its outputs
and has disabled the output as a means of protection.
Check the module for wiring faults.
Expansion
Power Trouble
The mains power supply is not connected to an
expansion module power supply.
Reconnect the mains power supply and ensure it is working
properly.
Expansion
Siren Trouble
The connection to an expansion module’s siren is
broken.
Repair the open circuit.
Expansion
Trouble
An expansion module or keypad is not reporting to the
control panel.
Ensure that the module is connected properly to the control
panel.
Tamper
Zone X
There is a problem with the wiring.
Check the zone and zone sensors for damage and repair any
faults.
Zone Problem,
Press OK
There is a problem with a zone or zones. Press OK to
identify the zone(s) and the problem condition.
One of the following messages is displayed when you
press OK.
CleanMe
A specific smoke detector (for
example, DP721) is dirty. The
panel detects a degree of
pollution in the chamber of the
fire/smoke detectors.
Clean the detection chamber of the smoke detector.
Table 1-5: Service messages
Message
Definition
Action