NX-8 Commercial Fire
7
TERM
DESCRIPTION
LOC
PG
Auxiliary Power
Overcurrent
The NX-8-CF will display a "Service Required" message on the keypad
when too much current is drawn from any device powered by the system.
This condition can be reported to the central station.
37
21
Box Tamper
The NX-8-CF has an input for a normally closed tamper switch (see
terminal drawing). The Box Tamper can be programmed to report and/or
sound the siren and/or the keypad. These terminals can be enabled or
disabled in programming.
37,
39
21
Built In Siren
Driver
The NX-8-CF has a built-in 112db siren driver. When desired, this built-in
driver can be easily converted to a 1-amp voltage output through
programming.
37
21
Bypass Toggle
This feature will enable the end user to toggle (turn on or off) the bypass
of an interior zone with the system armed by pressing BYPASS.
23
18
Cancel
If enabled, the NX-8-CF will send a "Cancel" report if when the system is
disarmed and the [Cancel] button is pressed within 5 minutes of an
alarm.
A
Dialer Delay
@
must be enabled in the
A
Characteristic Select
@
of
locations 110-149.
23
18
Communication
Formats
The NX-8-CF can report in Contact ID or SIA formats.
APPENDIX 1
44
Cross Zoning
This feature requires two or more trips on a zone or zones programmed
as "cross zones" within a specified time before reporting an alarm.
During the time between trips, the NX-8-CF can be programmed to
sound the keypad and/or the siren.
The NX-8-CF can also be
programmed to report an alarm after two or more trips on the same zone.
37,39,40,
110-149
21,
30-32
Dual / Split /
Multiple Reports
The NX-8-CF can send communication reports to three different phone
numbers for dual, split or multiple reports selectable by event or partition.
4, 10,
16
15-17
Duress Code
If a duress code is programmed the NX-8-CF will send a duress signal
whenever the panel is armed or disarmed with this code. If open/close
reports are sent, the user code will be 254.
44
24
Dynamic Battery
Test
The NX-8-CF can be programmed to perform a Dynamic Battery Test for
a selected duration the first time the panel is armed or disarmed every
day. If the panel is not armed or disarmed during the day it will perform
the test at midnight. The NX-8-CF can also be programmed to perform a
missing battery test every 12 seconds.
37, 40
21
Entry-Guard
This unique low-level arming mode has been developed to reduce the
most common source of false alarms. When armed as
A
Instant
@
, the
opening of any zones designated as "Entry Guard zone" will initiate the
keypad sounder and start the entry delay before creating an alarm. All
other zones will function as normal. This arming mode will encourage
system owners to use their system more frequently when the premises
are occupied.
For UL installations, this feature shall be DISABLED.
111-149
30-32
Exit Error
If enabled, the NX-8-CF will send an "Exit Error Report" if an entry/exit
zone is faulted at the instant the exit delay expires. This report will be
sent along with the user number that armed the system, if the panel is
not disarmed before the entry delay expires. The alarm report will also
be sent. Even if this feature is not enabled, the siren will sound if any
entry/exit zone is faulted at the instant the exit delay expires.
23
18