NX-8 Commercial Fire
17
LOCATION 13 - ACCOUNT CODE FOR PHONE #3
(6 segments, numerical data) The account code sent when Phone #3 is dialed is programmed in location 13. Program
a
A
10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program
all 6 segments. If location 6 is left unprogrammed, account code 1 will be used when the Phone #3 is dialed.
LOCATION 14 - COMMUNICATOR FORMAT FOR PHONE #3
(1 segment, numerical data) Location 14 contains the communicator format used to transmit to the receiver connected
to phone #3. Consult the instruction manual for your central station receiver to determine which format is compatible. If
this location contains a "0", Phone #3 will use the same format programmed for Phone #1 in Location 2.
LOCATION 15 - DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE #3
(2 segments, numerical data)
Segment 1, Dial Attempts
Segment 1 of Location 15 is used to enter the number of dial attempts (1 to 15 attempts) the communicator will
try to Phone #3 before ending the notification process. Factory default is "0" and the communicator will make
the same number of attempts as those programmed in location 3.
Segment 2, Phone # 3 Backup Control
Programming a "0" in Segment 2 of this location will cause the NX-8-CF to make the designated number of
attempts to Phone #2 before setting the "Fail To Communicate" condition and stop reporting. Programming a
"1" in this segment will cause the NX-8-CF to stop trying to communicate after the designated number of
attempts have been made to Phone #3. If a "2" is programmed in this segment, it will cause the NX-8-CF to
make the dial attempts in increments of two. The first two attempts will be made to Phone #3, the next two
attempts to Phone #2, then repeating until the total number of attempts designated in Segment 1 is completed.
REPORTING EVENTS TO PHONE NUMBER 3
Phone #3 can be used for a third receiver to multi-report or split report events. Phone #3 has two programming locations
that are used to select which events are reported to this phone number. Location 16 is used to select which events are
reported to Phone #3, and Location 17 is used to select which partitions are reported to Phone #3. If dual or split
reporting is not desired, location 16 and location 17 should be left at the factory default of "0". If multi-reporting or split
reporting is desired, and the split is based on the event type (such as alarm, open/close, etc.), then location 16 should
be used to select only those events that should be reported to Phone #3 and location 17 should be left at the factory
default of "0". If dual or split reporting is desired, and the split is based on partition, then location 16 should be
programmed to "0" and location 17 should be used to select those partitions that should be reported to Phone #3. If no
events should be reported to Phone #3, both locations should be "0".
LOCATION 16 - EVENTS REPORTED TO PHONE #3
(2 segments, feature selection data)
Segment 1
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming.
Segment 2
1 = Zone and
Box Tamper
and Tamper Restore.
2 = Auxiliary Power Overcurrent and Ground Fault and Restore for both.
3 = Sensor Missing and Restore.
4 = Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Reserved.
8 = Reserved.
LOCATION 17 - PARTITIONS REPORTED TO PHONE #3
(1 segment, feature selection data) Location 17 is used when events to be reported to a phone number are based upon
the partition regardless of the event. If this location is used, location 16 should be "0".
Technical Manuals Online! - http://www.tech-man.com