NX-8 Commercial Fire

4

Safety Symbol Legend

Warning

Indicates a procedure, practice, condition, or statement that, if not strictly
observed, could result in personal injury.
*

This symbol indicates electrical warnings and cautions.

Caution

Indicates a procedure, practice, condition, or statement that, if not strictly
observed, could result in damage to or destruction of equipment or property.
**

This symbol indicates general warnings and cautions.

Note

Indicates an essential or important procedure, instruction, condition, or
statement.

Tip

Indicates a user tip. Provides helpful information that is not normally defined
in regular use, but from an experienced user.

Technical Manuals Online! - http://www.tech-man.com

Содержание NetworX NX-8

Страница 1: ...NetworX Series NX 8 Commercial Fire Panel Installation and Startup Technical Manuals Online http www tech man com ...

Страница 2: ...formation of GE Interlogix USA and is furnished to its customer solely to assist that customer in the installation testing operations and or maintenance of the equipment described This document shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the written approval of GE Interlogix Please refer to the current GE Interlogix product catalog for...

Страница 3: ... START INSTALLATION 13 8 CONTROL PANEL PROGRAMMING LOCATIONS 14 REPORTING EVENTS TO PHONE NUMBER 1 14 REPORTING EVENTS TO PHONE NUMBER 2 16 REPORTING EVENTS TO PHONE NUMBER 3 17 9 DEFAULT ZONE TYPES CONFIGURATIONS 19 10 NX 8 CF PROGRAMMING WORKSHEETS 34 11 APPENDIX 1 44 12 APPENDIX 2 45 13 APPENDIX 3 46 14 NX 8 CF WIRING DIAGRAM 47 15 TERMINAL DESCRIPTION 48 KEYPAD MAXIMUM WIRE RUN 48 16 LOCAL TEL...

Страница 4: ...ocedure practice condition or statement that if not strictly observed could result in damage to or destruction of equipment or property This symbol indicates general warnings and cautions Note Indicates an essential or important procedure instruction condition or statement Tip Indicates a user tip Provides helpful information that is not normally defined in regular use but from an experienced user...

Страница 5: ...refer to the current GE Interlogix product catalog for detailed warranty information 2 ORDERING INFORMATION Minimum system configuration for local and central station protected premise unit UL Commercial Fire applications includes these individual modules PART DESCRIPTION MIN QTY NX 8 CF NX 8 CF Control Only 1 ea NX 148E CF Alphanumeric LCD Keypad for Commercial Fire applications red plastic 2 ea ...

Страница 6: ...es 41 23 Automatic Arming If programmed the NX 8 CF will Auto Arm at a specified time At this time the keypad will beep for 50 seconds before the panel arms If the arming process is stopped by typing a code on the keypad the NX 8 CF will attempt to arm 45 minutes later This time will be extended if there is activity in the building The Auto Arming of a partition can be programmed to be silent If c...

Страница 7: ...9 21 30 32 Dual Split Multiple Reports The NX 8 CF can send communication reports to three different phone numbers for dual split or multiple reports selectable by event or partition 4 10 16 15 17 Duress Code If a duress code is programmed the NX 8 CF will send a duress signal whenever the panel is armed or disarmed with this code If open close reports are sent the user code will be 254 44 24 Dyna...

Страница 8: ...his condition will display the Service Required message on the keypad 37 21 Group Bypass A designated group of zones can be programmed to bypass Prior to arming press BYPASS 0 BYPASS BYPASS For UL installations this feature shall be DISABLED 111 149 30 32 Immediate Restore By Zone The NX 8 CF can be programmed to send alarm and restore reports as soon as they occur or wait until the siren time has...

Страница 9: ...ing Report to the central station if an alarm occurs within 5 minutes after the panel is armed The user number that armed the system will also be sent 23 18 Re exit The NX 8 CF has the ability to restart the exit delay for a quick exit without disarming the system by pressing EXIT while the system is armed 23 18 Relays The NX 8 CF has two separate normally open and normally closed relay contacts f...

Страница 10: ...0 21 22 Temporal Siren Disable If disabled the Fire Siren will be steady and Fire Voltage Out will be the same as Burglary continuous Otherwise the Fire Siren will be temporal For UL installations this must be ENABLED 37 21 User Code A four or six digit entry code used to arm or disarm the system Walk Test Mode If enabled entering CHIME followed by a user code will allow a walk through zone test w...

Страница 11: ...cation entered is a valid location the top line of the LCD screen will display the location number on the left and the segment number on the right The bottom line of the display will show the current data This data will be displayed and entered according to the type of data used numerical binary or character data 1 NUMERICAL DATA The top line of the display will show the current location number on...

Страница 12: ...acter or ASCII data type This information is programmed using the bottom line of the display as a text editor Once a character location has been entered the current data will be displayed on the bottom line As is always the case the top line will display the current location and segment number The five 5 function keys as well as the up and down arrow to the right of the display are now used to edi...

Страница 13: ...or to enrolling modules To enroll the modules enter the Program Mode of the NetworX control panel When the Program Mode is exited the control will enroll the devices The enrolling process takes about 12 seconds during which time the Service Required will be displayed Once a module is enrolled if it is not detected by the control the Service Required will be displayed Please refer to the NX 148ECF ...

Страница 14: ... the designated number of attempts to Phone 2 before setting the Fail To Communicate condition and stop reporting Programming a 1 in this segment will cause the NX 8 CF to stop trying to communicate after the designated number of attempts have been made to Phone 1 If a 2 is programmed in this segment it will cause the NX 8 CF to make the dial attempts in increments of two The first two attempts wi...

Страница 15: ...one number by programming a 13 in the appropriate segment If tone dialing is desired program a 15 in the segment where tone dialing should begin If the entire number should be tone dialing program a 15 in the first segment Program an A11 for a Ar and a A12 for a A LOCATION 7 ACCOUNT CODE FOR THE PHONE 2 6 segments of numerical data The account code sent when Phone 2 is dialed is programmed in loca...

Страница 16: ...n location 10 should be programmed as 0 and location 11 should be used to select those partitions that should be reported to the Phone 2 If no events should be reported to Phone 2 both locations should be 0 LOCATION 10 EVENTS REPORTED TO PHONE 2 2 segments of feature selection data Segment 1 1 Alarms and Alarm Restores 2 Opening and Closings 3 Zone Bypass and Bypass Restores 4 Zone Trouble and Tro...

Страница 17: ...gment 1 is completed REPORTING EVENTS TO PHONE NUMBER 3 Phone 3 can be used for a third receiver to multi report or split report events Phone 3 has two programming locations that are used to select which events are reported to this phone number Location 16 is used to select which events are reported to Phone 3 and Location 17 is used to select which partitions are reported to Phone 3 If dual or sp...

Страница 18: ...re Segment 2 1 On enables the LED Extinguish feature 2 On enables the Require Code for Bypassing feature 3 On enables the Zone Bypassed Sounder Alert feature 4 Reserved 5 On enables Bypass toggle 6 On enables Silent Auto Arm 7 On enables the Automatic Instant feature 8 Reserved Segment 3 1 On enables Opening and Closing reports 2 On enables Zone Bypass reporting 3 On enables Zone Restore reporting...

Страница 19: ...n or partitions of the control panel that it resides in each time the zone is shorted Keyswitch arming will report as user 99 12 INTERIOR FOLLOWER WITH CROSS ZONE ENABLED This zone will be instant when the system is armed and no entry or exit delay is being timed It is delayed during entry and exit delay times If a Cross Zone is not being timed it will start a Cross Zone timer If a Cross Zone is b...

Страница 20: ...ore than 1 partition it will only be active when all partitions it resides in are armed A zone that resides in more than 1 partition will be reported to its lowest partition Location 28 has 8 segments Segment 1 corresponds to zone 9 and Segment 8 corresponds to zone 16 Segments 1 8 1 Partition 1 5 Partition 5 2 Partition 2 6 Partition 6 3 Partition 3 7 Partition 7 4 Partition 4 8 Partition 8 LOCAT...

Страница 21: ... 2 6 Partition 6 3 Partition 3 7 Partition 7 4 Partition 4 8 Partition 8 LOCATION 35 ZONES 41 48 ZONE TYPE 8 segments numerical data Location 35 contains the Zone type for zones 41 48 Segment 1 is for zone 41 Segment 8 is for zone 48 Default Zone Types are found in Table 9 1 on page 19 To customize a Zone Type see page 29 LOCATION 36 PARTITION SELECT ZONES 41 48 8 segments feature selection data L...

Страница 22: ... Reserved 3 On disables On Board 8 zones 4 On will allow two trips on same cross zone to activate an alarm 5 On will not allow zones that are force armed to report bypass 6 On enables Silent Exit option 7 Use internal crystal for clock 8 Disable Temporal Siren on Fire NOTE DO NOT disable for UL listed systems LOCATION 38 SWINGER SHUTDOWN COUNT Location 38 contains the number of trips during an arm...

Страница 23: ... 4 Enable Walk Test Mode Refer to GLOSSARY on page 6 5 8 Reserved LOCATION 42 GO TO PROGRAM CODE 6 segments numerical data Location 42 contains the Go To Program Code This location contains either a 4 or 6 digit code If the 6 digit code option is enabled in Location 41 THIS CODE MUST CONTAIN SIX 6 DIGITS If this option is not enabled in location 41 the last 2 segments digits will be ignored With t...

Страница 24: ...on 8 8 Partition 8 8 Partition 8 8 Partition 8 LOCATION 46 OUTPUTS 1 4 SPECIAL TIMING 4 segments feature selection data Location 46 contains special timing feature activation for outputs 1 4 Segments 1 and 2 correspond to relays outputs 1 and 2 while segments 3 and 4 correspond to auxiliary outputs 3 and 4 Segments 1 4 1 On if output should be timed in minutes Off if timed in seconds 2 On if outpu...

Страница 25: ...OB Function 1 24 Not Ready 50 Key FOB Function 2 25 Fire Events 49 50 require NX 408 NX 416 or NX 448 wireless receivers to operate If set to follow condition these events will be 1 second Notes When Event 48 is programmed it is possible to program a user code s authorization to select which output s a particular code will activate Refer to Assigning User Authority in the NX 148ECF installation ma...

Страница 26: ... be opened and is programmed to Auto Arm Location 55 the NX 8 CF will try to arm every 45 minutes for the duration of the closed period On days not selected here Aarm only after close window codes will not disarm Segment 1 is for partition 1 and segment 8 is for partition 8 Locations 52 and 53 for the opening and closing times for the open days Segment 1 8 1 Open on Sunday 2 Open on Monday 3 Open ...

Страница 27: ...xit times for partition 1 will be used Segment 1 Entry time 1 Entry time that will be used when a Delay 1 zone type initiates an entry delay Segment 2 Exit time 1 Exit time that will be used for all zones designated as Delay 1 Segment 3 Entry time 2 Entry time that will be used when a Delay 2 zone type initiates an entry delay Segment 4 Exit time 2 Exit time that will be used for all zones designa...

Страница 28: ...s long program all 6 segments LOCATION 99 PARTITION 5 FEATURE AND REPORTING SELECTIONS 3 segments numerical data Location 99 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system In addition certain communicator reports are enabled in this location Each of these features can be enabled by partition This location contains 3 segments with ei...

Страница 29: ... and exit times for partition 1 will be used Segment 1 Entry Time 1 Entry time that will be used when a Delay 1 zone type initiates an entry delay Segment 2 Exit Time 1 Exit time that will be used for all zones designated as Delay 1 Segment 3 Entry Time 2 Entry time that will be used when a Delay 2 zone type initiates an entry delay Segment 4 Exit Time 2 Exit time that will be used for all zones d...

Страница 30: ...arm 3 On if Zone Type will sound the temporal siren for alarm 4 On if Zone Type will chime 5 On if Zone Type can be bypassed 6 On if Zone Type is included in the group shunt 7 On if Zone Type is force armable 8 On if Zone Type is entry guard Segment 3 1 On enables Sprinkler Supervisory 2 On enables Double End Of Line Tamper zone Mainly used for tamper on wireless zones 3 On enables Trouble Reporti...

Страница 31: ...DE 1 segment numerical data Location 124 contains the event code sent for a Contact ID or SIA report The desired event code should be chosen from the list on page 45 The zone ID will be that zone that is in alarm LOCATION 125 ZONE TYPE 8 CHARACTERISTIC SELECT 3 segments feature selection data Use Zone Type Characteristic Selections described in Location 111 LOCATION 126 ZONE TYPE 9 ALARM EVENT COD...

Страница 32: ...hat is in alarm LOCATION 141 ZONE TYPE 16 CHARACTERISTIC SELECT 3 segments feature selection data Use Zone Type Characteristic Selections described in Location 111 LOCATION 142 ZONE TYPE 17 ALARM EVENT CODE 1 segment numerical data Location 142 contains the event code sent for a Contact ID or SIA report The desired event code should be chosen from the list on page 45 The zone ID will be that zone ...

Страница 33: ...ercial Fire 33 ZONE WORKSHEET 1 25 2 26 3 27 4 28 5 29 6 30 7 31 8 32 9 33 10 34 11 35 12 36 13 37 14 38 15 39 16 40 17 41 18 42 19 43 20 44 21 45 22 46 23 47 24 48 Technical Manuals Online http www tech man com ...

Страница 34: ...t 4 Sensor Low Battery 5 Expander Trouble 6 Fail To Communicate 7 Reserved 8 Reserved PHONE 1 SELECTING WHICH PARTITIONS REPORT TO PHONE 1 Segment 1 5 15 1 Partition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Partition 8 6 15 PHONE 2 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ __ 7...

Страница 35: ...4 Sensor Low Battery 5 Expander Trouble 6 Fail To Communicate 7 Reserved 8 Reserved PHONE 3 SELECTING WHICH PARTITIONS REPORT TO PHONE 3 Segment 1 17 17 1 Partition 1 2 Partition 2 3 Partition 3 4 Partition 4 5 Partition 5 6 Partition 6 7 Partition 7 8 Partition 8 18 22 18 RESERVED PARTITION 1 FEATURE SELECTION Segment 1 Segment 2 Segment 3 23 18 1 Quick Arm 2 Re Exit 3 Auto Bypass 4 Silent Panic ...

Страница 36: ... 8 Zone 24 Segments 1 2 3 4 5 6 7 8 30 20 Partition 1 Partition 2 Partition 3 Partition 4 Partition 5 Partition 6 Partition 7 Partition 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 31 20 ZONES 25 32 ZONE TYPES 6 6 6 6 6 6 6 6 _ _ _ _ _ _ _ _ ZONES 25 32 PARTITION SELECTION Segment 1 Zone 25 thru Segment 8 Zone 32 ...

Страница 37: ...st one time for keyswitch arming two times for disarming Segment 2 1 Convert siren driver to voltage out 2 Siren sounds for expander trouble required for U L 3 Immediate Restore by zone 4 Dynamic battery test performed upon arming 5 Battery missing test performed every 12 seconds 6 Manual bell test performed during r 4 test function 7 Manual communicator test performed during r 4 test function 8 B...

Страница 38: ...nt 6 Cross Zone Time 0 255 minutes 5 _____ Segment 7 Chime Time in 50 mS increments 0 255 3 _____ Segment 8 Dialer delay 0 255 seconds 0 _____ Segment 9 Fire Alarm Verification Time 120 240 sec 0 _____ 40 22 Segment 10 Reserved SPECIAL FEATURES Segment 1 41 23 1 2 Reserved 3 Enable Auto Cancel Abort 4 Enable Walk Test Mode 5 8 Reserved 42 23 GO TO PROGRAM CODE 9 7 1 3 0 0 _ _ _ _ _ _ GO TO PROGRAM...

Страница 39: ... alarm 48 24 Segment 2 Program the timing for relay 2 10 seconds AUXILIARY OUTPUT 3 EVENT TIME Segment 1 Program the event number for output 3 2 24 Hour Alarm 49 24 Segment 2 Program the timing for output 3 10 seconds AUXILIARY OUTPUT 4 EVENT TIME Segment 1 Program the event number for output 4 21 Armed State 50 25 Segment 2 Program the timing for output 4 0 Follow condition AUTOTEST CONTROL Segme...

Страница 40: ...re user code for bypassing zones 3 Bypass sounder alert 4 AC Power Low Battery sounder alert 5 Enable Bypass toggle 6 Enable Silent Auto Arm 7 Enable Automatic Instant 8 Reserved 1 Open Close 2 Bypass 3 Restore 4 Trouble 5 Tamper 6 Cancel 7 Recent Closing 8 Exit Error PARTITION 2 ENTRY EXIT TIMERS Segment 1 Entry Time 1 0 ___ Segment 2 Exit Time 1 0 ___ Segment 3 Entry Time 2 0 ___ 91 27 Segment 4...

Страница 41: ...s Tamper 1 LED Extinguish enable 2 Require user code for bypassing zones 3 Bypass sounder alert 4 AC Power Low Battery sounder alert 5 Enable Bypass toggle 6 Enable Silent Auto Arm 7 Enable Automatic Instant 8 Reserved 1 Open Close 2 Bypass 3 Restore 4 Trouble 5 Tamper 6 Cancel 7 Recent Closing 8 Exit Error PARTITION 5 ENTRY EXIT TIMERS Segment 1 Entry Time 1 0 ___ Segment 2 Exit Time 1 0 ___ Segm...

Страница 42: ...Panic 6 Auxiliary 1 7 Auxiliary 2 8 Multi Keypress Tamper 1 LED Extinguish enable 2 Require user code for bypassing zones 3 Bypass sounder alert 4 AC Power Low Battery sounder alert 5 Enable Bypass toggle 6 Enable Silent Auto Arm 7 Enable Automatic Instant 8 Reserved 1 Open Close 2 Bypass 3 Restore 4 Trouble 5 Tamper 6 Cancel 7 Recent Closing 8 Exit Error PARTITION 8 ENTRY EXIT TIMERS Segment 1 En...

Страница 43: ...__ ____ 128 31 ZONE TYPE 10 ALARM EVENT CODE 2 ___ 129 31 ZONE TYPE 10 CHARACTERISTIC SELECT 24 5 78 ____ ____ ____ 130 31 ZONE TYPE 11 ALARM EVENT CODE 3 ___ 131 31 ZONE TYPE 11 CHARACTERISTIC SELECT 3 0 0 ____ ____ ____ 132 31 ZONE TYPE 12 ALARM EVENT CODE 5 ___ 133 32 ZONE TYPE 12 CHARACTERISTIC SELECT 457 125 45678 ____ ____ ____ 134 32 ZONE TYPE 13 ALARM EVENT CODE 4 ___ 135 32 ZONE TYPE 13 C...

Страница 44: ...evice number 309 YR AC FAIL device number 301 AT AC RESTORE device number 301 AR BOX TAMPER device number 137 TA BOX TAMPER RESTORE device number 137 TR KEYPAD TAMPER 137 TA KEYPAD PANIC audible 120 PA KEYPAD PANIC silent 121 HA DURESS 121 HA KEYPAD AUXILIARY 1 110 FA KEYPAD AUXILIARY 2 100 MA RF SENSOR LOST zone number 381 T RF SENSOR RESTORE zone number 381 R SENSOR LOW BATTERY zone number 384 X...

Страница 45: ...15 GA Gas Alarm 16 KA Heat Alarm 17 WA Water Alarm 18 QA Emergency Alarm 19 SA Sprinkler Alarm 20 ZA Freeze Alarm The NX 8 CF has the ability to report Ademco Contact ID transmissions Each report in Contact ID consists of an Event Code and a Zone ID The zone ID is the zone that created the alarm The event code will come from the chart below and be programmed in the zone type event code Programmed ...

Страница 46: ...252 253 254 255 HARDWIRE EXPANDER NX216 NX 216E OUTPUT MODULE NX 508E Starting zone number Expander reported Address Dip Switch Setting Zone 9 All switches off 22 24 Switch 1 2 on 29 All switches off Zone 9 Switch 1 on 23 25 Switch 3 on 30 Switch 1 on Zone 17 Switch 2 on 16 26 Switch 1 3 on 31 Switch 2 on Zone 25 Switch 1 2 on 17 27 Switch 2 3 on Zone 33 Switch 3 on 18 28 Switch 1 2 3 on Zone 41 S...

Страница 47: ...NX 8 Commercial Fire 47 14 NX 8 CF WIRING DIAGRAM Technical Manuals Online http www tech man com ...

Страница 48: ... detectors and smoke detectors AUX PWR Connect positive wire of all powered devices except smoke detectors and keypads This terminal and KP POS are limited to 400mAtotal current when added together ZONE 8 Connect to one side of zone 8 loop Connect the other side to com terminal Open or short causes alarm Zone 8 may be used for a two wire smoke detector using a 680 Ω E O L resistor W3 must be set f...

Страница 49: ...uation The customer also has the right to bring a complaint to the FCC if he feels the disconnection is not warranted CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES The telephone company may make changes in its communications facilities equipment operations or procedures where such action is reasonably required and proper in its business Should any such change render the customers terminal e...

Страница 50: ... keypad option shall not be enabled UL has only verified compatibility with the following listed DACRs and formats Sure Gard SG MLR2 DG 2 9 10 12 13 14 Silent Knight 9000 2 12 FBI CP220FBI 13 and Ademco 685 2 11 12 and 13 Expander trouble must activate the siren Loc 37 Segment 2 LED 2 Use type FPL FPLR or FPLR cables as required by Article 760 of the National Electrical Code Section II Commercial ...

Страница 51: ...g the audible device require a minimum cutoff time of 4 minutes Section V Home Health Care applications must follow these requirements in addition to Section I A minimum of two 2 keypads are required for Home Health applications and each keypad must be set to a unique address For UL 1637 expander trouble must activate keypad sounder Loc 39 Seg 1 LED 8 For additional details please refer to the spe...

Страница 52: ... 500mS OPERATING TEMPERATURE 32 to 120 degrees F NX 148E CF LCD KEYPAD Current Draw 110 mA max w o Sounder 75 mA Dimensions 6 4 Wide 5 3 High 1 0 Deep METAL ENCLOSURE DIMENSION 11 25 Wide 11 25 High 3 50 Deep SHIPPING WEIGHT 9 lbs GE INTERLOGIX 1420 NORTH MAIN STREET GLADEWATER TEXAS 75647 Main 800 727 2339 Technical Support 800 727 2339 Outside the US 903 845 6941 Tech Support Fax 903 845 8409 Ma...